Supply
Electrical enclosure Matrix 6 from DASA with Frequency Converter supply should be done
as follows:
230V III + PE → Connect the 3 phases on L1, L2, L3 terminals and the earthing cable to the
corresponding terminal. Check on the central part of the dashboard that supply wires are in
230V and 0V terminal.
Engine and brake
To connect engine with frequency converter, you have to connect the engine 3 phases to U,
V and W terminals, and the earthing cable to the corresponding terminal.
Brake rectifier cables must be connected to the terminal with “FRENO”
indication.
Before operating with the door, check that engine plates are at 230V III position.
·
1.1.4. Frequency converter set up
Opening speed set up
Press MENU button on the frequency converter, and by turning and pressing in the middle
of the wheel, go to following parameter:
1CV converters
: RDY→CONF→HSP→65 (adjustable from 50 to 75)
2 and 3CV converters:
RDY→SET→HSP→60 (adjustable from 50 to 60)
Closing speed set up
Press MENU button on the frequency converter, and by turning and pressing in the middle
of the wheel, go to following parameter:
1CV converters:
RDY→CONF→FULL→FUN→P55→SP2→30 (adjustable from 15 to
50)
2 and 3CV converters:
RDY→ FUN→P55→SP2→30 (adjustable from 15 to 45)