4.4 Troubleshooting
Diagnostics
In case of operation faults or problems, the display flashes and the fault identification
code appears.
There are faults that cause permanent shutdown (marked with the letter “
A
”): to restore
operation just press the
reset
button (detail 6 -fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed; if the boiler fails to start, it is necessary to firstly
eliminate the fault.
Faults marked with the letter “
F
” cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
Table of faults
Table. 8 - List of faults
5. TECHNICAL DATA AND CHARACTERISTICS
fig. 26 - General view
Table. 9 - Key of figures cap. 5
Fault
code
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas flow to the
boiler and that the air has been
eliminated from the pipes
Ignition/detection electrode fault
Check the wiring of the electrode and
that it is correctly positioned and free
of any deposits
Faulty gas valve
Check the gas valve and replace it if
necessary
Insufficient gas supply pressure
Check the gas supply pressure
Trap blocked
Check the trap and clean it if
necessary
A02
Flame present signal with
burner off
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
A03
Overtemperature protection
activation
Heating sensor damaged
Check the correct positioning and
operation of the heating sensor
No water circulation in the system
Check the circulating pump
Air in the system
Vent the system
A04
Fume extraction duct safety
device activation
Fault F07 generated 3 times in the
last 24 hours
See fault F07
A05
Fan protection activated
Fault F15 generated for 1 hour (con-
secutive)
See fault F15
A06
No flame after ignition stage
(6 times in 4 minutes)
Ionisation electrode fault
Check the position of the ionisation
electrode and replace it if necessary
Flame unstable
Check the burner
Gas valve Offset fault
Check the Offset adjustment at
minimum power
air/fume ducts obstructed
Remove the obstruction from the flue,
fume extraction ducts and air inlet and
terminals
Trap blocked
Check the trap and clean it if
necessary
F07
High fume temperature
The fume probe detects an exces-
sive temperature
Check the exchanger
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F11
Return sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F12
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F13
Fume probe fault
Probe damaged
Check the wiring or replace the
fume probe
Wiring shorted
Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F15
Fan fault
No 230V power supply
Check the 8-pin connector wiring
Tachometric signal interrupted
Check the 8-pin connector wiring
Fan damaged
Check the fan
F34
Supply voltage under 170V Electric mains trouble
Check the electrical system
F35
Faulty mains frequency
Electric mains trouble
Check the electrical system
F37
Incorrect system water
pressure
Pressure too low
Fill the system
Water pressure switch damaged or
not connected
Check the sensor
F39
External probe fault
Probe damaged or wiring shorted
Check the wiring or replace the sensor
Probe disconnected after activating
the sliding temperature
Reconnect the external probe or
disable the sliding temperature
A41
Sensor positioning
Delivery sensor disconnected from
pipe
Check the correct positioning and
operation of the heating sensor
A42
Heating sensor fault
Sensor damaged
Replace the sensor
F43
Exchanger protection
activation.
No system H
2
O circulation
Check the circulating pump
Air in the system
Vent the system
F52
Heating sensor fault
Sensor damaged
Replace the sensor
A61
Controller
ABM03
fault
Controller
ABM03
internal error
Check the earth connection and
replace the controller if necessary.
A62
No communication between
controller and gas valve
Controller not connected
Connect the controller to the gas valve
Valve damaged
Replace the valve
A63
F64
A65
F66
Controller
ABM03
fault
Controller
ABM03
internal error
Check the earth connection and
replace the controller if necessary.
A23
A24
F20
F21
A26
F40
F47
Card parameter fault
Wrong card parameter setting
Check the card parameter and modify
it if necessary.
7
Gas inlet
95
Diverter valve
8
Domestic hot water outlet
104
Fuse
9
Cold water inlet
114
Water pressure switch
10
System delivery
136
Flow meter
11
System return
138
External probe (optional)
14
Safety valve
139
Remote timer control (optional)
16
Fan
154
Condensate drain pipe
32
Heating circulating pump
186
Return sensor
36
Automatic air vent
191
Fume temperature sensor
37
Cold water inlet filter
193
Trap
39
Flow regulator
194
DHW exchanger
42
DHW temperature probe
196
Condensate tray
44
Gas valve
241
Automatic bypass
56
Expansion tank
278
Double sensor ( Heating)
72
Room thermostat (not supplied)
340
Bypass pipe
74
System filling cock
350
Fan/Burner assembly
81
Ionisation/ignition electrode
A
ON/OFF switch (configurable)
Fault
code
Fault
Possible cause
Cure
10
8
7
9
11
44
39
136
37
193
32
114
14
36
186
56
191
196
350
81
95
194
278
74
42
340
cod. 3541C00
-
5HY
Summary of Contents for BLUEHELIX TECH C
Page 78: ......
Page 79: ......
Page 80: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it ...