background image

DIVAtech F37 D

6

EN

cod. 3541H480  -  Rev. 00 - 09/2015

Connection to collective flues

fig. 13 - Examples of connection to flues (

 = Air / 

 = Fumes)

Table. 7 - Typology

If the boiler is to be connected 

DIVAtech F37 D

 to a collective flue or a single flue with

natural draught, the flue or chimney must be expressly designed by professionally qual-
ified technical personnel in conformity with the current regulations and be suitable for
sealed chamber units equipped with fan.

4. SERVICE AND MAINTENANCE
4.1 Adjustments
Gas conversion

The unit can work on natural gas or LPG and is factory-set for use with one of these two
gases, as clearly shown on the packing and data plate. Whenever a different gas to that
for which the unit is arranged has to be used, the special conversion kit will be required,
proceeding as follows:
1.

Disconnect the power supply ahead of the boiler and close the gas cock;

2.

Replace the nozzles at the main burner and pilot burner, fitting the nozzles indicated
in the technical data table in cap. 5, depending on the type of gas used

3.

Connect the power supply ahead of the boiler and open the gas cock;

4.

Modify the parameter for the type of gas:

put the boiler in standby mode

press the DHW buttons (details 1 and 2 - fig. 1) for 10 seconds: the display
shows “

b01

“ flashing.

press the DHW buttons (details 1 and 2 - fig. 1) to set parameter 

00

 (for opera-

tion with natural gas) or 

01

 (for operation with LPG).

press the DHW buttons (details 1 and 2 - fig. 1) for 10 seconds.

the boiler will return to standby mode

5.

Adjust the minimum and maximum pressures at the burner (ref. relevant para-
graph), setting the values given in the technical data table for the type of gas used

6.

Apply the sticker, contained in the conversion kit, near the data plate as proof of the
conversion.

TEST mode activation

Press the heating buttons (details 3 and 4 - fig. 1) together for 5 seconds to activate the

TEST

 mode. The boiler lights at the maximum heating power set as described in the fol-

lowing section.
The heating and DHW symbols (fig. 14) flash on the display; the heating power will be
displayed alongside.

fig. 14 - TEST mode (heating power = 100%)

Press the heating buttons (details 3 and 4 - fig. 1) to increase or decrease the power
(min.=0%, max.=100%).
Press the DHW button 

"-"

 (detail 1 - fig. 1) and boiler power is immediately adjusted to

min. (0%). Press the DHW button 

"+"

 (detail 2 - fig. 1) and boiler power is immediately

adjusted to max. (100%).
If the TEST mode is activated and enough hot water is drawn to activate the DHW mode,
the boiler remains in TEST mode but the 3-way valve goes to DHW.
To deactivate the TEST mode, press the heating buttons (details 3 and 4 - fig. 1) for 5
seconds.
The TEST mode is automatically disabled in any case after 15 minutes or on stopping of
hot water drawing (if enough hot water is drawn to activate the DHW mode).

Pressure adjustment at the burner

Since this unit has flame modulation, there are two fixed pressure settings: minimum and
maximum, which must be those given in the technical data table according to the type of gas.

Connect a suitable pressure gauge to the  pressure point 

"B"

 downstream of the

gas valve.

Activate the TEST mode (see cap. 4.1).

Press the Eco/Comfort button for 2 seconds to access the gas valve Calibration mode.

The card goes to the setting “q02”; displaying the actually saved value, by pressing
the DHW buttons .

If the pressure gauge reading is different from the nominal maximum pressure, pro-
ceed by increases/decreases of 1 or 2 units of parameter “q02” by pressing the
DHW buttons : the value is stored after each modification;  wait 10 seconds for the
pressure to stabilise.

Press the heating button “-” (ref. 3 - fig. 1).

The card goes to the setting “q01”; displaying the actually saved value, by pressing
the DHW buttons .

If the pressure gauge reading is different from the nominal minimum pressure, pro-
ceed by increases/decreases of 1 or 2 units of parameter “q01” by pressing the
DHW buttons  : the value is stored after each modification; wait 10 seconds for the
pressure to stabilise.

Recheck both adjustments by pressing the heating buttons and adjust them if nec-
essary by repeating the above procedure.

Press the Eco/Comfort button for 2 seconds to return to the TEST mode.

Deactivate the TEST mode (see cap. 4.1).

Disconnect the pressure gauge.

Heating power adjustment

To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons (detail 3 - fig. 1) to increase or decrease the power (min. = 00 - max. =
100). Press the 

reset

 button within 5 seconds and the max. power will remain that just

set. Exit TEST mode (see sec. 4.1).

Type

Description

C2X

Intake and exhaust in common flue (intake and exhaust in same flue)

C4X

Intake and exhaust in common and separate flues , but undergoing similar wind conditions

C8X

Exhaust in single or common flue and wall intake

B3X

Intake from installation room by means of concentric duct (that encloses the exhaust) and exhaust in 
common flue with natural draught 

 IMPORTANT - THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION

C

8X

C

2X

C

4X

eco

comfort

reset

II

II

II

I I

I I I I I I

II

II

II

II

II

II

II

I I

I I I I I I

II

II

II

II

fig. 15 - Gas valve

A

 - Upstream pressure point

B

 - Downstream pressure point

I

 - Gas valve electrical connection

R

 - Gas outlet

S

 - Gas inlet

fig. 16 - Gas valve connection

TYPE SGV100
Pi max 65 mbar
24 Vdc - class B+A

R

B

I

A

S

~ 65

W

~ 24

W

1  2  3  4

Summary of Contents for DIVAtech F37 D

Page 1: ... cod 3541H480 Rev 00 09 2015 DIVAtech F37 D F A 85 76 54 51 81 104 B C D E 175 127 330 700 450 330 196 110 115 115 110 A B C D E F EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE ...

Page 2: ...ection button 8 DHW symbol 9 DHW mode 10 Summer mode 11 Multifunction 12 Eco Economy mode 13 Heating 14 Heating symbol 15 Burner lit and actual power level flashing during combustion fault function 16 Service Tool connection 17 Water gauge Indication during operation Heating A heating demand generated by the Room Thermostat or Remote Timer Control is in dicated by flashing of the hot air above the...

Page 3: ... fig 1 for 5 seconds to access the Sliding temperature menu the display shows CU flashing Use the DHW buttons detail 1 fig 1 to adjust the curve from 1 to 10 according to the characteristic By setting the curve to 0 sliding temperature adjustment is disabled Press the heating buttons detail 3 fig 1 to access parallel curve offset the display shows OF flashing Use the DHW buttons detail 1 fig 1 to ...

Page 4: ...ing systems and compatible with the materials of the boiler and system 3 4 Gas connection The gas must be connected to the relevant union see figure on cover in conformity with the current regulations with a rigid metal pipe or with a continuous surface flexible s steel tube installing a gas cock between the system and boiler Make sure all the gas connec tions are tight 3 5 Electrical connections ...

Page 5: ...ergo similar wind conditions within 50 cm C3X Roof vertical exhaust and intake Inlet outlet terminals like for C12 C5X Wall or roof exhaust and intake separate or in any case in areas with different pressures The exhaust and intake must not be positioned on opposite walls C6X Intake and exhaust with separately certified pipes EN 1856 1 B2X Intake from installation room and wall or roof exhaust IMP...

Page 6: ...T mode press the heating buttons details 3 and 4 fig 1 for 5 seconds The TEST mode is automatically disabled in any case after 15 minutes or on stopping of hot water drawing if enough hot water is drawn to activate the DHW mode Pressure adjustment at the burner Since this unit has flame modulation there are two fixed pressure settings minimum and maximum which must be those given in the technical ...

Page 7: ... Code fault Fault Possible cause Cure A01 No burner ignition No gas Check the regular gas flow to the boiler and that the air has been eliminated from the pipes Ignition detection electrode fault Check the wiring of the electrode and that it is correctly positioned and free of any deposits Faulty gas valve Check the gas valve and replace it if necessary Gas valve wiring disconnected Check the wiri...

Page 8: ...4 System filling cock 14 Safety valve 81 Ignition and detection electrode 16 Fan 95 Diverter valve 19 Combustion chamber 114 Water pressure switch 22 Burner 138 External probe not supplied 27 Copper exchanger for heating and hot water 139 Room unit not supplied 28 Fume manifold 187 Fume baffle 29 Fume outlet manifold 194 DHW exchanger 32 Heating circulating pump 241 Automatic bypass 36 Automatic a...

Page 9: ... h 1 48 Burner nozzles G31 n x Ø 17 x 0 79 Gas supply pressure G31 mbar 37 Max gas pressure at burner G31 mbar 35 0 Min gas pressure at burner G31 mbar 5 0 Max gas delivery G31 kg h 3 10 Min gas delivery G31 kg h 1 10 Max working pressure in heating bar 3 PMS Min working pressure in heating bar 0 8 Max heating temperature C 90 tmax Heating water content litri 1 5 Heating expansion tank capacity li...

Page 10: ...iring diagram fig 21 Electrical circuit A Important Before connecting the room thermostat or the remote timer control remove the jumper on the terminal block 81 1kW L N 230V 50 Hz 16 N L 32 L N T T 278 T 42 4 3 2 1 44 38 114 ABM01 LC32 3 2 1 95 72 139 138 ...

Page 11: ...er FERROLI S p A Address Via Ritonda 78 a 37047 San Bonifacio VR Italy declares that this unit complies with the following EU directives Gas Appliance Directive 2009 142 Efficiency Directive 92 42 Low Voltage Directive Electromagnetic Compatibility Directive EN ...

Page 12: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it ...

Reviews: