SIZING OF ADDITIONAL EXPANSION VESSELS:
Deduct from the value given in the table the 10
litre vessel supplied.
Note:
1.
Fill C.H. installation to min. 1.5 bar.
2.
Expansion vessel must be fi tted to central
heating return pipe.
3.
The standard 10 litre expansion vessel is
charged to 1 bar.
4.
The additional expansion vessel should be
charged to 1 bar.
SAFETY VALVE
SETTING (bar)
VESSEL CHARGE
PRESSURE (bar)
INITIAL SYSTEM
PRESSURE (bar)
TOTAL WATER
CONTENT of SYSTEM
3.0
0.5 1.0 1.5
1.0 1.5 2.0 1.5 2.0 2.0
EXPANSION VESSEL VOLUME (litres)
LITRES
25 3.5 6.5 13.7 4.7 10.3 8.3
50 7.0 12.9 27.5 9.5 20.6 16.5
75 10.5 19.4 41.3 14.2 30.9 24.8
100 14.0 25.9 55.1 19.0 41.2 33.1
125 17.5 32.4 68.9 23.7 51.5 41.3
150 21.0 38.8 82.6 28.5 61.8 49.6
175 24.5 45.3 96.4 33.2 72.1 57.9
200 28.0 51.8 110.2 38.0 82.4 66.2
0.140 0.259 0.551 0.190 0.412 0.33
For syst. volumes other than
those given above, mult. the syst.
volume by the factor across