DOMINA 80 E
43
5.08 Adjusting central heating system pressure
The pressure of water in the central heating system, read on the control panel pressure gauge, is adjusted
as described in paragraph 3.11 page 35.
N.B. -
To avoid incurring unnecessary expense, in the event of boiler shut down, check that this is not
caused by a lack of electricity or gas, or low water pressure before calling the Customer Technical Service
Helpline.
5.09 Gas conversion
The following adjustment and conversion operations must be carried out by competent personnel.
FERROLI Limited accepts no liability for damage to property or personal injury resulting from tampering
with the boiler by unauthorised persons.
To convert the boiler from Nat Gas to LPG and vice versa, the main burner injectors must be replaced.
Minimum and maximum pressures must then be adjusted on the gas valve (see Adjustment page 41).
Note: After converting the boiler from natural gas to liquid gas, fit the orange plate in the conver-
sion kit near the data plate.
Note: injector diameters and pressures at the main burner are given in Technical Data (page 5).