Circulator (230v/50Hz)
Located on the heating circuit return, it is connected directly to the exchanger
via special forks and connected to the system via a threaded brass section.
It has three delivery/head levels (see diagram). Changing the delivery/head
changes the speed of the water flowing through the boiler exchanger and as
a result the temperature difference ( T) between heating delivery and
return. Clearly, increasing the delivery of the circulator decreases T and vice
versa. If it is not used for a long time, the impeller might jam due to debris
in the water. With the front screw it is possible to access the impeller, which
can be freed with the aid of a screwdriver. The connection to the expansion
tank and the air separator is installed on the pump casing.
Checks
If the pump doesn't work:
Check that the impeller is free to turn by turning the screw on the front
with a screwdriver.
Check that both the card and the pump connection are powered.
If there is no power supply, check the card.
If there is power, change the pump.
Air separator
This is used to expel the air in the heating circuit automatically. On boilers
with a twin heat exchanger, it is located on the pump casing. It is normally
accessible either via the fork or by simply unscrewing it from its seat.
Key
1 - 2 - 3 =
Pump selector position
A =
Losses of head 24kW version
B =
Losses of head 30kW version