DOMINA N 80 DGT
23
For further accessories please refer to:
"Flue system manual for room sealed boiler"
Attention
:
Resistance of fl ue restrictor (if req.)
is included (see table on page 18)
Remove
the
fl ue restrictor.
The
fl ue and air pipes must have an inclination
downward equal to 3% from boiler to outside.
Example of calculation for wall inlet/outlet
with 2 pipe system
maximum total fl ue length: 48 metres
Fig. 24
REF. N° OF PIECES DESCRIPTION
CODE
LENGTH OR
REDUCTION
1
1
Air bend 80 mm R/D = 0,75
1,5 m
2
13
Horizontal air pipe
13,0 m
3
1
Air wall terminal
2,0 m
4
1
Air inlet closing ß ange
Ñ
5
1
Flue bend 80 mm R/D = 0,75
2,5 m
6
12
Horizontal ß ue
24,0 m
7
1
Air wall terminal outlet ß ue
5,0 m
TOTAL
48,0
m
Example of wall inlet/outlet
2 pipe application
Example of roof i
nlet/outlet
Example of direct roof fl ue outlet
and wall air inlet
3.08.3 Example of other installation with two pipe systems
Fig. 25
Fig. 27
Fig. 26