N.B. -
The gas pressures at the burner and gas fl ows during the
central heating phase
given in the table refer
to
nominal boiler output
. To reduce this output (where necessary), gas pressure must be reduced until the
required output level is reached (see fi gures 4 and 5).
During domestic hot water production
, gas pressures to the burner
must correspond to the maximum
output given in table for the type of gas
.
Gas pressure must be adjusted during maximum draw-off of domestic hot water.
• Maximum working temperature for central heating fl ow: 85°C
• Maximum temperature of domestic hot water: 55°C, adjustable between 40°C and 55°C.
• Minimum domestic cold water pressure required for 95% heat input:
-
Flow restrictor fi tted (standard) - 1,2 bar;
-
Flow restrictor removed - 0,5 bar
MODEL
Heat output
Heat input
Domestic hot
water heat
input
Boiler water
contents
Domestic hot
water contents
kW
kW
kW
kW
kW
Litres
Litres
Domina N 80 DGT
23,8
9,7
25,8
11,5
23,8
1,5
0,8
MODEL
Connections
Expansion vessel
Max. working
pressure
central
heating
circuit
Max.
working
pressure hot
water circuit
1
2
3
4
5
Capacity
Pre-pressurising
value
Ø
Ø
Ø
Ø
Ø
Litres
bar
bar
bar
Domina N 80 DGT
3/4”
1/2”
1/2”
1/2”
3/4”
7
1
3
6
MODEL
Main injectors (mm)
Gas flow rates to main burners
for central heating
Gas valve
Ø1/2
G20 - NG G31 -LPG
G20 - NG
G31 -LPG
Ø
Ø
m
3
/h
kg/h
Domina N 80 DGT
12x1,30
12x0,77
2,73
2,00
H. V K4105G
MODEL
Gas supply pressures
working
Gas pressure at main burner for central heating
Safety valve
G20
G31
G20
G31
min.
m
min.
m
mbar
mbar
mbar
mbar
mbar
mbar
bar
Domina N 80 DGT
20
37
2,5
11,8
7,8
36,0
MODEL
Domestic hot
water production
with
∆
t 30
°
C
Domestic hot
water production
with
∆
t 35
°
C
Max. working
pressure domestic
hot water
Protection
level
Weight
G20
G31
l/min.
l/min.
mbar
mbar
kg
Domina N 80 DGT
11,3
9,7
11,8
36,0
IP44
38
Technical Data