35
DOMITOP HF 24 - 30 E
FERELLA GOLD HF 24 - 30 MEL
Version - 09.2002
Flow Diagram 2
Checking Heating Operation
Flow Diagram 3
Controllo Ventilatore/Circuito Fumi
Wait for 2 minutes
Set the temperature for
heating to maximum
Make sure the room
thermostat is activated
Is LED4 blinking?
Does the circulator turn?
YES
YES
Proceed with
diagram 3
Is the relay
RY 101 closed?
Check and if
necessary change
the main card
NO
Is LED4 blinking?
Check and if necessary
change the heating sensor
NO
NO
Is the relay
RY100 closed?
YES
Proceed with
diagram 4
NO
Check the limit
thermostat
Check and if
necessary change
the pump
NO
Check the electrical
connections of
the pump
NO
YES
YES
YES
YES
YES
YES
Does the fan turn?
Is the relay RY3 closed?
Proceed with diagrams 2-3
NO
Are there 230V at the
fan terminals?
Check the electrical connection
of the air pressure switch
NO
Check and if necessary
change the air pressure switch
NO
Check and if necessary
change the fan
Is the air pressure
switch activated?
NO
Check and if
necessary change
the air pressure
switch
Is the pressure
difference in the air
pressure switch
180 Pascal?
Proceed with
diagram 5
NO
Check and
clean the fan
Check that the air inlet
and fume outlet are
correct and clean
Check that the Venturi tube
and the air pressure switch
tubes are clean
Check that
the diaphragm is correct
NO