ECONCEPT 35 C
19
GB
cod. 3540F320 - 02/2007 (Rev. 00)
Opening the casing
To open the boiler casing (fig. 17):
1. Unscrew the screws
A
2. Open by turning the panel “
B
3. Lift and take off the panel “
B
fig. 17 - Opening the casing
Combustion analysis
Combustion analysis can be carried out through the sampling points for air (
detail 1
) and fumes (
detail 2
) shown in
fig. 18.
To carry out the measurement:
1. Open the air and fume sampling points
2. Insert the probes
3. Press the
"+"
and
"-"
buttons for 5 seconds to activate TEST mode
4. Wait 10 minutes for the boiler to stabilise
5. Carry out the measurement
For natural gas the CO
2
reading must be between 8.7 and 9 %.
For LPG the CO
2
reading must be between 9.5 and 10 %.
A
Analyses carried out with the boiler not stabilised can cause measurement errors.
fig. 18 - Combustion analysis
A
A
B
1
2
1
2