27
3.4 Troubleshooting
Diagnostics
The boiler features an advanced self-diagnostic system. In the case of an fault in operation, the display flashes
and the code identifying the fault appears. The faults marked with the letter
“A”
cause the permanent shut-
down of the boiler. To reset operation the boiler must be restarted manually, pressing the
“R”
(reset) button.
The faults marked by the letter
“F”
cause temporary shut-down and are reset automatically as soon as the
value returns within the boiler’s normal operating range.
The following table lists a number of indications for resolving the faults signalled by the boiler. Adjustmens
on the appliance must only be carried out by Qualified Personnel, such as the personnel from the FERROLI
Customer Technical Service Centre. For any operations on the appliance or which require the opening of the
boiler, always request the assistance of the service centre.
Failed burner
assembly ignition
• No gas
• Ignition or detection
electrode fault
• Defective gas valve
• Faulty full auto control
• Check that the gas flow to the boiler
is correct and that air has been
purged from the piping
• Check the wiring to the electrodes
and that these are positioned
correctly and free of deposits
• Check and replace the gas valve
if required
Safety thermostat
activation
• Outlet sensor not active
• No system circulation
• Check the correct positioning and
operation of the outlet sensor
• Check the pump
Flue safety device
intervention
• Flue partially blocked
or insufficient
• Check the efficiency of the flue,
the flue gas exhaust pipes and
the outlet terminal
No flame following the
ignition phase
• Low gas pressure
• Faulty ionisation probe
• Faulty full auto control
• Check as necessary
Insufficient water system
pressure
• System empty
• Fill the system to 1.5 bar
Fan fault
• Fan not powered
• Defective fan
• Check the wiring to
the fan
• Replace the fan
Fault
Possible cause
Solution