Combustion analysis
It is possible to analyse the combustion through the air sampling (
detail 2
) and fume sampling (
detail 1
) points shown
in fig. 30.
To take the measurement:
1. Open the air and fume sampling points
2. Insert the probes
3. Press
the
"+"
and
"-" buttons for 5 seconds to activate TEST mode
4. Wait 10 minutes for the boiler to stabilise
5. Take the measurement
For natural gas the CO
2
reading must be between 8.7 and 9 %.
For LPG the CO
2
the reading must be between 9.5 and 10 %.
A
Analyses made with an unstabilised boiler can cause measurement errors.
fig. 30 - Combustion analysis