ECONCEPT TECH 35 A
25
EN
cod. 3540I341 - 04/2008 (Rev. 00)
F13
Fume sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F15
Fan fault
No 230V power supply
Check the wiring of the 3-pole connector
Tachometric signal interrupted
Check the wiring of the 5-pole connector
Fan damaged
Check the fan
F34
Supply voltage under 170V
Power supply trouble
Check the electrical system
F35
Mains frequency fault
Power supply trouble
Check the electrical system
F37
Incorrect system water
pressure
Pressure too low
Fill the system
Water pressure switch not con-
nected or damaged
Check the sensor
F39
External probe fault
Probe damaged or wiring
shorted
Check the wiring or replace the sensor
Probe disconnected after acti-
vating the sliding temperature
Reconnect the external probe or disable the sliding
temperature
A41
Sensor positioning
Delivery sensor disconnected
from the pipe
Check the correct positioning and operation of the
heating sensor
F42
Heating sensor fault
Sensor damaged
Replace the sensor
Fault
code
Fault
Possible cause
Cure