background image

ENERGY TOP B

73

EN

cod. 3540S738  -  Rev. 00  -  01/2014

TEST mode activation

Press the heating buttons 

+/-

 (details 3 and 4 - fig. 1) together for 5 seconds to activate

TEST

mode. The boiler lights at the maximum heating power (Range Rated) set as de-

scribed in the following section.

The heating symbol (detail 13 - fig. 1) and DHW symbol (detail 9 - fig. 1) flash; the heat-
ing power will appear alongside.

fig. 55 - TEST mode (heating power = 100%)

To deactivate Test mode, repeat the activation sequence.

The TEST mode is automatically disabled in any case after 15 minutes.

Only for model ENERGY TOP B 160 - 250

In TEST mode, press the button (detail 7 - fig. 1) to obtain the following operation:

Top boiler shell on; bottom boiler shell off.

Top boiler shell off; bottom boiler shell on.

Top boiler shell on; bottom boiler shell on.

Heating Capacity Adjustment (RANGE RATED)

A

This is a 

“RANGE RATED”

 boiler (according to EN 483) and can be adjusted

to the system's thermal requirement by setting the maximum heating capacity
for operation in heating mode, as follows:

Put the boiler in TEST mode (see sec. 4.1).

Press the 

heating buttons

 (details 3 and 4 - fig. 1) to increase or decrease the power (min.

= 00 - max. = 100). See the diagram “Heating Capacity Adjustment” (fig. 56).

Press the 

reset button

 (detail 8 - fig. 1) within 5 seconds and the maximum heating

capacity will remain that just set. Exit TEST mode (see sec. 4.1).

A

THE HEATING CAPACITY ADJUSTMENT THUS SET ENSURES KEEPING
OF THE EFFICIENCY VALUES DECLARED ON cap. 5.4

Heating power adjustment diagram

A =

 kW  -  

B =

 Electronic Board Parameter

fig. 56

4.2 Start-up

B

Checks to be made at first lighting, and after all maintenance operations that
involved disconnection from the systems or an operation on safety devices or
parts of the boiler:

Before lighting the boiler

Open any on-off valves between the boiler and the systems.

Check the tightness of the gas system, proceeding with caution and using a soap
and water solution to detect any leaks in connections.

Check correct prefilling of the expansion tank (ref. sec. 5.4).

Fill the water system and make sure all air contained in the boiler and the system
has been vented, by opening the air vent valve on the boiler and any vent valves on
the system. 

Fill the condensate trap and check correct connection of the condensate elimination
system.

Make sure there are no water leaks in the system, DHW circuits, connections or boiler.

Check correct connection of the electrical system and efficiency of the earthing system

Make sure the gas pressure value for heating is that required.

Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler

Checks during operation

Turn the unit on as described in sec. 2.3.

Make sure the fuel circuit and water systems are tight.

Check the efficiency of the flue and air-fume ducts while the boiler is working.

Check the correct tightness and functionality of the condensate elimination system
and trap.

Make sure the water is circulating properly between the boiler and the systems.

Make sure the gas valve modulates correctly in the heating and domestic hot water
production phases.

Check proper boiler lighting by doing several tests, turning it on and off with the room
thermostat or remote control.

Using  a  combustion  analyser  connected  to  the  boiler  fume  outlet,  check  that  the
CO

2

 content in the fumes, with the boiler operating at max. and min. output, corre-

sponds to that given in the technical data table for the corresponding type of gas.

Make sure the fuel consumption indicated on the meter matches that given in the
technical data table on sec. 5.4.

Check the correct programming of the parameters and carry out any necessary cus-
tomization (compensation curve, power, temperatures, etc.).

4.3 Maintenance

Periodical check

To keep the unit working properly over time, it is necessary to have qualified personnel
make an annual check that includes the following tests:

The control and safety devices (gas valve, flow meter, thermostats, etc.) must func-
tion correctly.

The fume extraction circuit must be fully efficient.

The airtight chamber must be sealed

The air-fume end piece and ducts must be free of obstructions and leaks

The condensate evacuation system must be efficient with no leakage or obstructions.

The burner and exchanger must be clean and free of scale. When cleaning, do not
use chemical products or wire brushes.

The electrode must be free of scale and properly positioned.

The gas and water systems must be airtight.

The water pressure in the cold water system must be about 1 bar; otherwise, bring
it to that value.

The circulation pump must not be blocked.

The expansion tank must be filled.

The gas flow and pressure must correspond to that given in the respective tables.

A

The boiler casing, panel and aesthetic parts can be cleaned with a soft damp
cloth, possibly soaked in soapy water. Do not use any abrasive detergents and
solvents.

4.4 Troubleshooting

Diagnostics

The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the
display will flash together with the fault symbol (detail 20 - fig. 1) indicating the fault code.

There are faults that cause permanent shutdown (marked with the letter "

A

"): to restore

operation just press the 

RESET

 button (detail 8 - fig. 1) for 1 second or RESET on the

optional remote timer control if installed; if the boiler fails to start, it is necessary to firstly
eliminate the fault.

Other faults (marked with the letter “

F

”) cause temporary shutdowns that are automati-

cally reset as soon as the value returns within the boiler's normal working range, except
for fault 

F37

 which is reset by turning the unit off and then on again  with button 

14

 of

fig. 1.

 !"!#

!$%

$%&'% #

EANH,.EA-,6

IIIIIII

IIII

III

III

IIII

IIIIIIIIIII

IIIIIIII

IIII

100

90

80

70

60

50

40

30

20

10

0

0

20

40

60

80

100

120

140

160

180

200

220

240

260

 

!

80

"#

$

12

5"

#$

16

0"

#$

250

"#$

Summary of Contents for ENERGY TOP B 125

Page 1: ...N Y MANTENIMIENTO TR KULLANMA KURULUM VE BAKøM TALIMATLARø EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATION D INSTALLATION ET D ENTRETIEN RO INSTRUCğIUNI DE UTILIZARE INSTALARE ùI ÎNTRETINERE RU ɊɍɄɈȼɈȾɋɌȼɈ ɉɈ ɗɄɋɉɅɍȺɌȺɐɂɂ ɆɈɇɌȺɀɍ ɂ ɌȿɏɈȻɋɅɍɀɂȼȺɇɂɘ UA ȱɇɋɌɊɍɄɐȱə Ɂ ȿɄɋɉɅɍȺɌȺɐȱȲ ɆɈɇɌȺɀɍ ɌȺ ɈȻɋɅɍȽɈȼɍȼȺɇɇə ...

Page 2: ...uminium finned tube exchangers with steel premix burners housed in a vertical cabinet in epoxy powder coated steel resistant to atmospheric agents The plumbing circuits of the exchangers each equipped with its own local circulating pump run into system delivery and return manifolds inside the module The control sys tem has a microprocessor user interface with a large display and advanced cascade c...

Page 3: ...a max of 90 C fig 8 DHW temperature adjustment with optional hot water tank installed Use the DHW buttons details 1 and 2 fig 1 to adjust the temperature from a min of 10 C to a max of 65 C fig 9 Room temperature adjustment with optional room thermostat Using the room thermostat set the temperature required in the rooms Room temperature adjustment with optional remote timer control Using the remot...

Page 4: ...e Configurations in line fig 15 Configuration in line example with 4 modules Table 2 Configurations in line Heating temperature adjustment Adjustment can be made from the Remote Timer Control menu and the boiler control panel DHW temperature adjustment with optional hot water tank installed Adjustment can be made from the Remote Timer Control menu and the boiler control panel Summer Winter Switcho...

Page 5: ...system characteristics In the presence of water harder than 25 Fr it is advisable to use suitably treated water in order to avoid possible scaling in the boiler caused by hard water or corrosion pro duced by aggressive water Due to its low thermal conductivity scaling even just a few mm thick causes significant overheating of the generator walls with consequent serious problems Water treatment is ...

Page 6: ...Fit the bolts supplied on the flanges from inside the first module making them come out the flanges in the second module Partially tighten the nuts on the bolts from inside the second module Before tightening the nuts make sure all the seals are correctly positioned and fit the condensate drain pipes of the two modules see fig 49 Tighten the nuts and repeat the connection operations for the U pipe...

Page 7: ...eans Transparent Param eters Menu In Information Menu Hi History Menu and rE History Menu Reset Se lect tS and press the RESET button The card has 29 transparent parameters also modifiable from Remote Control Service Menu Press the Heating buttons to scroll the list of parameters in increasing or decreasing or der Press the DHW buttons to modify the value of a parameter the change will be au tomat...

Page 8: ... with a bipolar switch whose contacts have a minimum opening of at least 3 mm interposing fuses of max 3A between the boiler and the line It is important to re spect the polarities LINE brown wire NEUTRAL blue wire EARTH yellow green wire in making connections to the electrical line During installation or when changing the power cable the earth wire must be left 2 cm longer than the others B The u...

Page 9: ... with the pro visions concerning the positioning of wall and or roof terminals and the minimum distanc es from windows walls ventilation openings etc Manifold ducts and flue must be suitably sized designed and made in compliance with the current standards They must be made of suitable materials i e resistant to heat and corrosion smooth on the inside and hermetic In particular joints must be conde...

Page 10: ... the special manifolds optionals given in the table The choice of diameter must be made according to the total power of the bank of units respecting that given in the table Use a starting kit for each bank containing manifold plug and trap and a suitable number of manifolds one for each ENERGY TOP B 80 125 and two for each ENERGY TOP B 160 250 90 bends and manifold extensions are also available fo...

Page 11: ... Fix the fume manifold brackets in the special holes arranged in the modules see fig 38 for side by side modules and fig 39 for opposed modules fig 38 fig 39 Arrange the height and slope of the manifold by means of the special holes in the brack ets fig 40 and fig 41 fig 40 fig 41 Couple together the fume manifolds and the trap cap using slippery agent or grease see fig 42 fig 42 Ø 300 B 2G 3G 1G ...

Page 12: ... them on the fume manifold Then tighten screw D fig 47 fig 46 fig 47 3 6 Condensate drain B The boiler has an internal condensate drain trap connected to an internal con densate outlet manifold Condensate outlet connection using one generator fig 48 Condensate drain connection with one generator A Place the Ø40 pipe 1 not supplied on the side of the generator B Slide the pipe 2 towards the arrow s...

Page 13: ...do the two fixing screws B and remove the fan assembly as indicated in fig 50 for the model ENERGY TOP B 80 160 and in for fig 51 the model ENERGY TOP B 125 250 fig 50 model ENERGY TOP B 80 160 fig 51 model ENERGY TOP B 125 250 6 Undo the screws C and remove fan D fig 52 only model ENERGY TOP B 125 250 fig 52 model ENERGY TOP B 125 250 7 Undo the fixing screws E fig 53 model ENERGY TOP B 80 160 an...

Page 14: ...g Check the correct tightness and functionality of the condensate elimination system and trap Make sure the water is circulating properly between the boiler and the systems Make sure the gas valve modulates correctly in the heating and domestic hot water production phases Check proper boiler lighting by doing several tests turning it on and off with the room thermostat or remote control Using a co...

Page 15: ...g shorted Wiring disconnected F11 Return sensor fault Sensor damaged Check the wiring or replace the sensor Wiring shorted Wiring disconnected F12 DHW sensor fault Sensor damaged Check the wiring or replace the sensor Wiring shorted Wiring disconnected F13 Fume sensor fault Sensor damaged Check the wiring or replace the sensor Wiring shorted Wiring disconnected F14 Delivery sensor 2 fault Sensor d...

Page 16: ...ng pump not supplied 138 External probe not supplied 139 Remote timer control not supplied 154 Condensate drain pipe 179 Non return valve 186 Return sensor 191 Fume temperature sensor 193 Trap 196 Condensate tray 215 Air inlet reducer 220 Ignition card 252 3 way drain and shutoff cock 253 Shutoff cock 278 Double sensor Safety Heating 298 Cascade temperature sensor not supplied 299 Input 0 10 Vdc 3...

Page 17: ...ain components Model ENERGY TOP B 80 125 fig 59 General view model ENERGY TOP B 80 125 Model ENERGY TOP B 160 250 fig 60 General view model ENERGY TOP B 160 250 10 7 11 10 7 11 193 32 196 82 220 44 29 215 36 16 278 252 253 154 179 14 186 114 38 81 345 191 10 11 7 10 11 7 ...

Page 18: ... Water circuit Model ENERGY TOP B 80 125 fig 61 Water circuit model ENERGY TOP B 80 125 Model ENERGY TOP B 160 250 fig 62 Plumbing circuit model ENERGY TOP B 160 250 16 36 44 81 82 29 196 278 22 186 154 193 252 253 32 14 179 38 345 11 10 7 114 10 7 11 ...

Page 19: ... 3 26 9 18 3 26 9 Efficiency Pmax 80 60 C 98 0 98 0 98 0 98 0 Efficiency Pmin 80 60 C 98 5 98 5 98 5 98 5 Efficiency Pmax 50 30 C 106 106 106 106 Efficiency Pmin 50 30 C 107 5 107 5 107 5 107 5 Efficiency 30 109 109 109 109 Gas supply pressure G20 mbar 20 20 20 20 Max gas delivery G20 m3 h 7 94 12 38 15 88 24 76 Min gas delivery G20 m3 h 1 8 2 65 1 8 2 65 Gas supply pressure G31 mbar 37 37 37 37 M...

Page 20: ...n the terminal block J J 230V 50KL 16 278 191 186 16 32 V1 V2 44 X1 X3 X2 98 L N 1 2 3 4 5 7 8 9 10 11 12 1 2 3 4 5 1 2 3 4 5 7 8 9 10 M 3O15A J J 6BC12P 16 278 191 186 114 16 32 V1 V2 44 X1 X3 X2 A 25 2 27 28 29 30 1 2 3 4 1 2 3 4 5 6 D12 X01 X04 X03 X05 13 14 15 1 17 18 19 20 21 22 23 24 299 139 72 138 298 42 4 5 7 8 9 10 11 12 F F F F 300 301 95 302 130 307 72B 6BC12E 6BC12P 6BC12E 306 38 114 3...

Page 21: ...ttiva Compatibilità Elettromagnetica 2004 108 Presidente e Legale rappresentante Cav del Lavoro Dante Ferroli IT Uygunluk beyani ømalatçi FERROLI S p A Adres Via Ritonda 78 a 37047 San Bonifacio VR bu cihazin asagida yer alan AET EEC yönergelerine uygunluk içinde oldugunu beyan etmektedir 2009 142 Gazla çalistirilan üniteler için Yönetmelik 92 42 Randiman Verimlilik Yönetmeligi Yönerge 2006 95 Düs...

Page 22: ...ɤɬɢɜɚɦ CEE Ⱦɢɪɟɤɬɢɜɚ ɩɨ ɝɚɡɨɜɵɦ ɩɪɢɛɨɪɚɦ 2009 142 Ⱦɢɪɟɤɬɢɜɚ ɩɨ Ʉ ɉ Ⱦ 92 42 Ⱦɢɪɟɤɬɢɜɚ ɩɨ ɧɢɡɤɨɦɭ ɧɚɩɪɹɠɟɧɢɸ 2006 95 Ⱦɢɪɟɤɬɢɜɚ ɩɨ ɷɥɟɤɬɪɨɦɚɝɧɢɬɧɨɣ ɫɨɜɦɟɫɬɢɦɨɫɬɢ 2004 108 ɉɪɟɡɢɞɟɧɬ ɢ ɭɩɨɥɧɨɦɨɱɟɧɧɵɣ ɩɪɟɞɫɬɚɜɢɬɟɥɶ Ʉɚɜɚɥɶɟɪɟ ɞɟɥɶ ɥɚɜɨɪɨ ɩɨɱɟɬɧɵɣ ɬɢɬɭɥ ɩɪɢɫɭɠɞɚɟɦɵɣ ɝɨɫɭɞɚɪɫɬɜɨɦ ɡɚ ɡɚɫɥɭɝɢ ɜ ɪɭɤɨɜɨɞɫɬɜɟ ɩɪɨɦɵɲɥɟɧɧɨɫɬɶɸ Dante Ferroli RU DeclaraĠie de conformitate Producător FERROLI S p A Adresă Via Ritonda...

Page 23: ......

Page 24: ......

Page 25: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it ...

Reviews: