22
OPTIMAX HE PLUS 25 S
Cod. 3540R540 - 02/2009 (Rev. 00)
B
Connection to collective flues or single flues with natural draught
If you are then going to connect the
OPTIMAX HE PLUS 25 S
boiler to a collective flue or a single flue
with natural draught, the flue must be expressly designed by professionally qualified technical personnel
in conformity with the standards and rules in force.
In particular, flues must have the following characteristics:
• Be sized according to the method of calculation stated in the standard
• Be airtight to the products of combustion, resistant to the fumes and heat and waterproof for the
condensate
• Have a circular or square cross-section (some hydraulically equivalent sections are permissible), with
a vertical progression and with no constrictions
• Have the flue conveying the hot fumes adequately distanced or isolated from combustible mate-
rials
• Be connected to just one unit per floor, for at most 6 units in all (8 if there is a compensation duct or
opening)
• Have no mechanical suction devices in the main ducts
• Be at a lower pressure, all along their length, under conditions of stationary operation
• Have at their base a collection chamber for solid materials or condensation of at least 0.5 m, equipped
with a metal door with an airtight closure.
2.7 Condensate outlet connection
The boiler is equipped with an internal air-trap to drain off the condensate. Fit the inspection coupling
A
and the hose
B
, pushing it on for approximately 3 cm and securing it with a clamp.
Fill the air-trap with approximately 0.5 ltrs of water and connect the hose to the waste system, or
soakaway.
0,5 lt.
A
fig. 21