PEGASUS D 30 K 100 LN
43
EN
5.2 Pressure losses
Circulating pump head / pressure losses
fig. 28
5.3 Technical data table
Data
Unit
Value
Number of elements
no.
4
Max. heating capacity
kW
32.2
(Q)
Max. heat output in heating
kW
30.2
(P)
Efficiency Pmax (80-60°C)
%
93.7
Efficiency 30%
%
91.8
Efficiency class Directive 92/42 EEC
NOx emission class
5
Burner nozzles G20
no. x Ø
3 x 2.90
Gas supply pressure G20
mbar
20
Gas diaphragm G20
Ø mm
4.8
Max. pressure downstream of gas valve G20
mbar
16
Max. gas delivery G20
m
3
/h
3.41
Burner nozzles G31
no. x Ø
3x1.65
Gas supply pressure G31
mbar
37
Gas diaphragm G31
Ø mm
No diaphragm
Max. gas pressure at burner G31
mbar
35
Max. gas delivery G31
kg/h
2.52
Max. working pressure in heating
bar
6
(PMS)
Min. working pressure in heating
bar
0.8
Max. heating temperature
°C
95
(tmax)
Heating water content
L
12.5
Heating expansion tank capacity
L
10
Heating expansion tank prefilling pressure
bar
1
Max. working pressure in hot water production
bar
9
Min. working pressure in hot water production
bar
0.1
DHW content
L
100
DHW expansion tank capacity
L
4
DHW expansion tank prefilling pressure
bar
3
DHW flow rate Dt 30°C l/10min.
l/10 min.
220
DHW flow rate Dt 30°C l/h
l/h
800
Protection rating
IP
X0D
Power supply voltage
V/Hz
230/50
Electrical power input
W
110
Electrical power input in hot water production
W
90
Empty weight
kg
245
0
1
2
3
4
5
6
7
0
0.5
1
1.5
2
Q
[m
3
/h]
H
[m H
2
O]
3
1
2
2.5
3
cod. 3540T306 - Rev. 01 - 02/2015