16
ENGLISH
ENGLISH
OVERALL DIMENSIONS
Storage
unit
A
C
B
B
Minimum space required for operation
To correctly install the unit, comply with the measurements for the free area that must
be left around the machine, as shown in the figure.
This will ensure good air circulation, allow the unit to operate correctly and facilitate
future maintenance work.
Allow a distance of at least 3/4 of the height of the actual machine when installing shel-
ters over this latter.
NOTE: The unit must not be surrounded by more than three walls as this would
impede the ventilation required for it to operate properly.
The distances must be doubled if the unit is to be installed in a pit.
Model
16
19
24
30
30/3
38
38/3
42
50
MU
A
400
mm
B
150
mm
C
600
mm
Remove the packing materials and, using a fork-lift truck, lift the Storage Module and set it in the required position. Keep the unit
in a vertical position without tilting it when it is transported. High protection against the transmission of vibrations is obtained by
fitting pads of resilient material (neoprene, etc.) between the machine’s bearing stands and the floor. The measurements to