Wiring diagrams for models 16 - 19 - 24 - 30 - 38 - SINGLE-PHASE UNIT
ELECTRICAL CONNECTIONS
(1):
For lengths less than 20 meters.
(2):
With reference to flexible cable with polychloroprene sheathing type
H07RN-F
.
NOTE: Automatic circuit-breaker IL and the section of the cables must be checked and sized to suit the real conditions of use.
Automatic switch at installer’s charge.
3
1
4
2
C20N
C10
multi 9
6000
2
0-OFF
230V
0-OFF
MERLIN GERIN
on off
mode
Set
2
25
24
26 1
3 4
ALLALL
R1A
R1A
R1A
R1A
P2
P1
RATG
MP
P1
P2
26
25
24
on/off
mode
MC739_0
GROUND TER-
MINAL
A
IL
STORAGE PUMPS (opt)
INSTALLED BY MANUFACTURER
POWER SUPPLY 230v-1-50Hz
FOR NON-STANDARD CIRCULATORS
1.5mm2 WIRES. MAX LENGTH 20m TYPE H07RH-F
OR DEPENDING ON INSTALLATION. SEE SPECIFIC
STANDARDS. MAX CURRENT DRAW 3A
230V-1-50Hz POWER SUPPLY
REMOTE DIGITAL INPUT
FOR ON/OF MODE. 1.5mm2 WIRES. H07 RN-F
REMOTE DIGITAL INPUT
FOR SUMMER/WINTER MODE. 1.5mm2 WIRES. H07 RN-F
CONNECTION A
T
INST
ALLER’S
CHARGE
1mm
2
WIRES. MAX LENGTH 100m
TYPE
H07 RN-F OR DEPENDING ON INST
ALLA
TION.
CONSUL
T
SPECIFIC ST
ANDARDS
STORAGE ANTIFREEZE HEATING ELEMENT (opt)
INSTALLED BY MANUFACTURER. MAXIMUM
POWER 250W POWER SUPPLY 230v-1-50Hz
POWERED CONTACT
INSTALL 12V 50mmA MAX RELAY
IMPORTANT:
THE INSTALLER MUST FIT AN AUTOMATIC
BIPOLAR CIRCUIT-BREAKER ON THE POWERING LINE
WITH A BREAKING CAPACITY OF NOT LESS THAN 10KA
230V-1-50Hz POWER SUPPLY
ACTIVATED WITH MACHINE IN ALARM STATUS
CONDENSER
TERMINAL BOARD
REMOTE CONTROL
REMOTE CONTROL (opt)
Model
16
19
24
30
38
MU
Type of power supply
230/1/50
V/Ph/Hz
Automatic
switch IL
(1)
C60N 20A
C60N 25A
C60N 25A
C60N 32A
C60N 40A
/
Cable section
(2)
A
2.5
2.5
2.5
4
6
mm
2
Table 1