28
ENGLISH
ENGLISH
USEFUL HEAD
Units 16-19-24-30 with Storage and Pumping Module
The graph below illustrates the useful head values (
kPa
) depending on the water flow rate in (
liters/second
): the Standard or
High Head Pumping Module can be used with each of models 16-19-24-30.
The operating range is delimited by the minimum and maximum values given in the next table.
Useful head is the one at the outlet of the Storage and Pumping Module minus all the loss of pressure values of the wet compo-
nents of the unit and Storage and Pumping Module.
Limits to operation (Standard Head)
Useful head (kPa)
Water flow rate (l/s)
Unit size
16
19
24
30
MU
NOTES
Graph reference
1
2
3
4
/
Q=
Water flow rate
Lower limit value
Q
0.13
0.17
0.18
0.21
l\s
Upper limit value
0.37
0.44
0.48
0.53
l\s
Limits to operation (High Head)
Unit size
16
19
24
30
MU
NOTES
Graph reference
5
6
7
8
/
Q=
Water flow rate
Lower limit value
Q
0.13
0.17
0.18
0.21
l\s
Upper limit value
0.50
0.58
0.62
0.66
l\s
0
20
40
60
80
100
120
140
160
180
200
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
- - -
Useful Head supplied by
Storage Module in the High Head Version
Useful Head supplied by Storage
Module in the Standard Version
Head of Standard and High Head Versions mod. 16 - 19 - 24 - 30
1
2
3
4
5
6
7
8
MODEL OF UNIT
16 - 19
24 - 30
Storage and
Pumping Module model
30
33
STANDARD VERSION
SAA8
SAA10
HIGH HEAD VERSION
SAA9
SAA11
Unit matches with Storage and Pumping Module Accessory