30
ENGLISH
ENGLISH
IN COOLING MODE (units IR / IP)
IN HEATING MODE (IP units)
Operating limits
The graphs below give the operating ranges within which correct operation of the units is guaranteed.
Use of the units in conditions differing from those indicated will void the warranty with which the product is supplied.
5
25
35
45 46
5
7
10
[°C]
[°C B.S.]
7
-6
35
45
50
[°C]
[°C B.S./Ur=87%]
20
WATER OUTLET
TEMPERATURE
OUTDOOR AIR
TEMPERATURE
WATER OUTLET
TEMPERATURE
OUTDOOR AIR
TEMPERATURE
Entity
Limit value in the cooling mode
Limit value in the heating mode
Minimum thermal gradient of the water
°C
3
3
Maximum thermal gradient of water
°C
8
8
Unit
16
19
24
30
30/3
38
38/3
42
50
MU
Maximum operating
pressure on wet side
1000
kPa
Pumping & Storage module
30
33
55
MU
Maximum operating
pressure on wet side
300
kPa
Maximum operating pressure on wet side
NOTE:
Never use more than 40% of brine in Multiple stage pump versions of units operating in conjunction with the
Storage and Pumping Module.
!
OPERATING RANGE