- 5 -
1.2 DATI TECNICI UNITÀ
1.2 UNIT TECHNICAL DATA
serie series
+
(1) Multiple = Multivelocità > 3
Man = Manuale da selettore o tastiera;
0-10V = Da potenziometro o tastiera;
VSD = A portata costante o modulazione da sensore qualità/umidità aria
(2) Aria esterna -5°C 80% UR; aria ambiente 20°C 50% UR
(3) Aria esterna 32°C 50% UR; aria ambiente 26°C 50% UR
(4) Secondo regolamento UE 1253/2014: alla pressione nominale; condizioni di
temperatura e umidità riferite a EN 308
(5) Livello di potenza sonora alle condizioni di funzionamento nominali
(1) Multiple = Multispeed > 3
Man = Manual by selector switch or control panel;
0-10V = By potentiometer or control panel;
VSD = Constant flow control or modulation by air quality or air humidity sensor
(2) Outside air at -5° 80% RH; room air at 20°C 50% RH
(3) Outside air at 32° 50% RH; room air at 26°C 50% RH
(4) Refeer to EU 1253/2014 regulation: at nominal pressure; air conditions refer to
EN 308 standard
(5) Sound power level at nominal working conditions
MODELLO /
MODEL
40
40 E
75
75 E
100 100 E 150 150 E 200 200 E 320 320 E 400 E 500 E
Portata aria nominale /
Nominal air flow
m
3
/h
400
400
750
750
1000
1000
1500
1500
2050
2050
3200
3200
3800
4700
Pressione statica utile nominale /
Nominal external static pressure
Pa
160
160
120
120
130
130
160
160
120
120
180
180
200
200
Pressione statica utile massima /
Maximum external static pressure
Pa
160
340
120
210
130
520
160
500
120
540
180
375
330
200
Alimentazione elettrica /
Electrical power supply
V/ph/Hz
230 / 1 / 50
230 / 1 / 50-60
Potenza assorbita massima totale /
Total full load power input
kW
0.35
0.56
0.68
0.56
1.41
2.12
1.41
2.12
1.41
2.12
3.29
2.35
2.07
2.07
Corrente assorbita massima totale /
Total full load amperage
A
1.5
2.4
2.9
2.4
6.0
9.0
6.0
9.0
6.0
9.0
14.0
10.0
8.8
8.8
LIMITI OPERATIVI /
WORKING LIMITS
40
40 E
75
75 E
100 100 E 150 150 E 200 200 E
320 320 E 400 E 500 E
Condizioni di temperatura - umidità limite esterne
Outdoor temperature - humidity working limits
°C / %
-5 … +45 °C / 5 … 95%
Condizioni di temperatura - umidità limite esterne con accessorio RMS
Outdoor temperature - humidity working limits with RMS option
°C / %
-15 … +45 °C / 5 … 95%
Condizioni di temperatura - umidità limite interne
Indoor temperature - humidity working limits
°C / %
+10 … +35 °C / 10 … 90%
VENTILATORI /
FANS
40
40 E
75
75 E
100 100 E 150 150 E 200 200 E
320 320 E 400 E 500 E
Tipologia motore /
Motor typology
AC
EC
AC
EC
AC
EC
AC
EC
AC
EC
AC
EC
EC
EC
N° velocità (1) /
Number of speeds (1)
3
Multiple
3
Multiple
3
Multiple
3
Multiple
3
Multiple
3
Multiple Multiple Multiple
Controllo ventilazione (1) /
Fan control (1)
Man 0-10V Man 0-10V Man
0-10V
VSD
Man
0-10V
VSD
Man
0-10V
VSD
Man
0-10V
VSD
0-10V
VSD
0-10V
VSD
Potenza assorbita nominale totale /
Total nominal power input
kW
0.17
0.16
0.38
0.30
0.52
0.49
0.80
0.76
1.00
0.84
1.79
1.77
1.78
2.19
Corrente assorbita nominale totale /
Total nominal load amperage
A
0.7
0.7
1.6
1.3
2.2
2.1
3.4
3.2
4.3
3.6
7.6
7.5
7.6
9.3
Efficienza statica dei ventilatori secondo (UE) n.327/2011
Static efficiency of fans
%
N.A. 32.7% 38.6% 32.7% 38.6% 53.2% 38.6% 53.2% 40.4% 55.9% 43.4% 59.8% 66.9% 66.9%
RECUPERATORE DI CALORE /
HEAT EXCHANGER
40
40 E
75
75 E
100 100 E 150 150 E 200 200 E
320 320 E 400 E 500 E
Efficienza termica invernale
(2)
/
Winter thermal efficiency
(2)
%
83.6% 83.6% 82.9% 82.9% 81.6% 81.6% 83.3% 83.3% 83.7% 83.7% 86.8% 86.8% 84.1% 84.2%
Potenza termica recuperata
(2)
/
Heating recovery capacity
(2)
kW
2.76
2.76
5.13
5.13
6.73
6.73
10.30 10.30 14.14 14.14 22.90 22.90 26.34 32.62
Temperatura aria mandata
(2)
/
Supply air temperature
(2)
°C
15.9
15.9
15.7
15.7
15.4
15.4
15.8
15.8
15.9
15.9
16.7
16.7
16.0
16.1
Efficienza termica estiva
(3)
/
Summer thermal efficiency
(3)
%
75.5% 75.5% 75.9% 75.9% 74.5% 74.5% 75.1% 75.1% 75.6% 75.6% 78.0% 78.0% 75.0% 75.1%
Potenza frigorifera recuperata
(3)
/
Cooling recovery capacity
(3)
kW
0.61
0.61
1.15
1.15
1.50
1.50
2.27
2.27
3.12
3.12
5.02
5.02
5.73
7.10
Temperatura aria mandata
(3)
/
Supply air temperature
(3)
°C
27.5
27.5
27.4
27.4
27.5
27.5
27.5
27.5
27.5
27.5
27.3
27.3
27.5
27.5
Efficienza termica a secco
(4)
/
Dry thermal efficiency
(4)
%
75.9% 75.9% 76.4% 76.4% 75.0% 75.0% 75.6% 75.6% 76.0% 76.0% 76.3% 76.3% 75.5% 75.6%
DATI SPECIFICI ECODESIGN /
ECODESIGN SPECIFIC DATA
40
40 E
75
75 E
100 100 E 150 150 E 200 200 E 320 320 E 400 E 500 E
Tipologia dichiarata /
Declared typology
NRVU - BVU
Potenza specifica interna di ventilazione - SFP int
(4)
Internal specific fan power of ventilation components - SFP int
(4)
W/(m
3
/s)
740
705
934
742
1105
1059
1102
1048
1078
898
1054
1040
949
935
Potenza massima specifica interna dei componenti della ventilazionePint_limite)
Maximum internal specific fan power of ventilation components (SFPint_limit)
W/(m
3
/s) 1170
1170
1171
1171
1118
1118
1116
1116
1105
1105
1066
1066
1017
982
Velocità frontale alla portata nominale /
Face velocity at design flow rate
m/s
0.93
0.93
1.36
1.36
1.81
1.81
2.00
2.00
1.83
1.83
2.06
2.06
2.44
2.42
Perdita di pressione dei componenti interni della ventilazione (
Δ
ps,int)
Internal pressure drop of ventilation components (
Δ
ps,int)
Pa
140
140
119
119
179
179
202
202
177
177
194
194
252
248
Massimo trafilamento esterno dell'involucro
Declared maximum external leakage rates of the casing of ventilation units
%
< 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5 < 3,5
Massimo trafilamento interno o flusso residuo
Declared maximum internal leakage rate for bidirectional ventilation units or carry over
%
< 4
< 4
< 4
< 4
< 4
< 4
< 4
< 4
< 4
< 4
< 4
< 4
< 4
< 4
Consumo annuo calcolato di energia dei filtri F7 e M5 (8760 h di funzionamento)
Calculated annual energy consumption of the F7 and M5 filters (8760 h of operation)
kWh/a
613
487
1228
1448
2320
1684
3945
2862
4601
3325
5562
4036
5456
6649
Livello di potenza sonora irradiato dall'involucro
(5)
Sound power level (LWA)
(5)
dB(A)
58
57
61
60
61
59
64
61
64
59
68
64
66
68