System manual CECX / SSI Interface module CECX-C-2G1
CECX-II 29-10
On leaving the factory all modules are set to address 0 and both covers are
closed.
Note
Modules of the same type that are installed within the same line must have
different address switch positions. Different modules (e.g. CECX-C-2G2
and CECX-C-2G1) may have the same address switch positions.
The lids for the K-Bus plug and the address switch must remain locked at
the last module in the line (to protect it against pollution and damage
through electrostatic discharge on contact).
29.7 Operating behavior
29.7.1 Operating mode of the module
29.7.1.1 Failure of supply voltage
If the supply voltage fails, the
Module Status
variable is set to TRUE.
29.7.1.2 Response to sensor failure
In case of sensor failure, the
Channel Status
variable of the affected
channel is set to TRUE.
When the fault is corrected the following status variable is again set to
FALSE.
29.8 Disposal
29.8.1 Disposal of the module
•
The symbol with the crossed-out waste container means that electrical
and electronic devices including their accessories must not be dis-
posed of in the household garbage.
•
The materials are recyclable in accordance with their labeling. By dis-
posing of such used devices correctly, you can ensure that they can be
reused, their raw materials recycled or put to another use, and you will
be making an important contribution to the protection of our environ-
ment!
Summary of Contents for CECX-X-C1 Series
Page 1: ...Manual Controller Modular CECX CECX X C1 CECX X M1 761886 1112c en ...
Page 2: ...1112c en ...
Page 4: ......
Page 6: ...1112c en ...
Page 7: ...CECX modular control system CECX modular control system ...
Page 46: ...CECX modular control system CECX I 38 ...
Page 47: ...System manual CECX ...
Page 48: ...CECX II ...
Page 56: ...Content System Manual CECX VIII ...
Page 58: ...System manual CECX Product design CECX II 0 2 ...
Page 68: ...System manual CECX Safety notes CECX II 2 6 ...
Page 76: ...System manual CECX System overview CECX II 3 8 ...
Page 84: ...System manual CECX General assembly and installation instructions CECX II 4 8 ...
Page 118: ...System manual CECX Operating behavior CECX II 8 6 ...
Page 122: ...System manual CECX Disposal CECX II 10 2 ...
Page 124: ...System manual CECX Technical data CECX II 11 2 ...
Page 166: ......
Page 180: ......
Page 212: ......
Page 232: ......
Page 248: ......
Page 260: ......
Page 278: ......
Page 294: ......
Page 308: ......
Page 412: ......
Page 426: ......
Page 500: ...System manual CECX Bus link module CECX B CO CECX II 34 64 ...
Page 501: ...The library Ethernet lib The library Ethernet lib ...
Page 505: ...The library EventData lib The library EventData lib ...
Page 511: ...The library IncEnc lib The library IncEnc lib ...
Page 517: ...The Festo_EasyIP lib library ...
Page 532: ......
Page 535: ...The library PLCService lib The library PLCService lib ...
Page 542: ...The library PLCService lib CECX VII 6 ...
Page 543: ...The library SysLibComEx lib The library SysLibComEx lib ...
Page 547: ...The Festo_Motion lib library ...
Page 584: ......
Page 585: ...The Festo_PartDetector lib library ...
Page 601: ...FED VipWin interface ...
Page 630: ......