CESA-GW-AS-PB Description
32
Now the new slave can be connected to the AS-i network. After connecting, the
current address of the slave is displayed as "OLD ADDRESS"and the message
"CONNECT NEW SLV" disappears.
To assign a new address to the slave the menu entry "NEW ADDRESS" must be
selected. Afterwards the new address can be selected by using the arrow but-
tons. The selected address is assigned by selecting "PRG" on the menu and
pressing the OK button.
If an error occurs while addressing a slave, one of the following error messages is
displayed for about 2 seconds:
6.7
SLAVE TEST TOOL
Main menu ||
SLAVE TEST TOOL
||
After selecting the menu SLAVE TEST TOOL a warning message is displayed,
pointing out, that it is possible during this test that outputs are set and that the
host may loose control over the network.
Pressing the OK button continues with the actual test, ESC cancels the process.
In the proceeding menu the slave to be tested has to be selected by entering the
slave address.
Afterwards, testing the selected slave is started by confirming the menu entry
"Test".
SLAVE ADR TOOL
CONNECT
OLD ADDRESS 21A
NEW ADDRESS 03B
PRG
Failed: SND: slave with old address has not been detected.
Failed: SD0: slave with address 0 already exists.
Failed: SD2: chosen slave address already exists.
Failed: DE: AS-i slave address cannot be deleted.
Failed: SE: error setting new address for AS-i slave.
Failed: AT: new address for AS-i slave could be stored temporarily only.
Failed: RE: error reading extended ID1-code.
WARNING:
OUTPUTS MAY BE
SET AND HOST MAY
LOOSE CONTROL.