CESA-GW-AS-PB Description
61
A rising edge of F2 and F3 switch the master to the desired mode.
A rising edge of the "LOS master bit" effects that all bits in the
LOS
are set. A fall-
ing edge effects that all bits are deleted.
7.1.3.2
EC flags and AS-i watchdog
In addition to ec-flags, the AS-i watchdog flags will be transferred in diagnostic
data too.
Diagnostic data are assembled as follows:
7.1.3.3
AS-i 16-bit data
In addition to the access via the command interfaces, the 16-bit data for or by the
slaves with 16-bit value can by exchanged cyclically (profile 7.3., S-7.4, S-6.0, S-
7.5, S-7.A.8, S-7.A.9, S-7.A.A). Competing writing access attempts on analog
output data will not be blocked by each other. If analog data for a particular slave
are being transmitted both cyclically and acyclically with the command interface
or via DP/V1 connections, the acyclically transmitted values will be overwritten by
the cyclically transmitted values.
AS-i 16-bit data can be transmitted in a reserved data area. Therefore accessing
analog data is as easy as accessing digital data.
Offline: 0 = online
1 = offline
LOS-Master-Bit 0 =
offline by configerror deactivated
1 =
offline by configerror activated
ec-flags (high):
bit 0: periphery fault
bit 1 … bit 2: reserved
bit 3: failure redundant 24 V
bit 4: earth fault
bit 5: over voltage
bit 6: noise
bit 7: duplicate address
ec-flags (low):
bit 0: configuration error
bit 1: slave with address0 detected
bit 2: auto_address_assignment not possible
bit 3: auto_address_assingment available
bit 4: configuration mode actice
bit 5: not in normal operation
Information!
A-slaves map the data on channels 1 and 2.
B-slaves map the data on channels 3 and 4.