CESA-GW-AS-PB Description
45
6.10.2
ACTUAL CONFIG (actual slave configuration)
Main menu || DIAGNOSIS ||
ACTUAL CONFIG
||
The flag is set if the automatic addressing is possible. This means that exactly
one slave has failed.
Bit 2: Auto_Addr_Asn
The flag is set if automatic addressing is possible (AUTO_ADDR_ENABLE =
1; no "incorrect" AS-i slave is connected to AS-i).
Bit 1: LDS.0
The flag is set,if an AS-i slave with address 0 has been detected.
Bit 0: Config_OK
The flag is set if the projected configuration is equal to the actual configura-
tion.
Byte 3
Bit 0: Data_Exch_Act
If the flag "Data Exchange Active" is set, the data exchange with AS-i slaves is
possible during the data exchange phase. If the bit is not set, the data
exchange with AS-i slaves is inhibited. Instead of data telegrams READ_ID
telegrams will be sent.
The bit is set by the AS-i master at the beginning of the offline phase.
Bit 1: Offline
This bit is set if the operating mode is supposed to be changing to offline or is
already offline.
Bit 2: Auto_Addr_Ena
This flag indicates if automatic addressing has been disabled (bit = 0) or ena-
bled (bit = 1) by the user.
ACTUAL CONFIG
0A | 1A-C
....
30A-X | 31A-D
| 1B-X
....
30A | 31B-F
HELP:
X O.K.
D DETECTED ONLY
UNKNOWN SLAVE
P PROJ. ONLY
MISSING SLAVE
C TYPE CONFLICT
F PERIPH. FAULT
A DUPLICATE ADDR