1.6.1 Connecting the screening
•
Clamp the screening of the fieldbus cable under the
clip of the Festo plug (see diagram).
PLEASE NOTE
The cable clip in the Festo plug is only capacitively
connected internally with the metal housing of the
Sub-D plug.
This is to prevent equalizing currents from flowing
via the screening of the fieldbus cable (see diagram).
1
2
Screening connection, cable clip
Only capacitively connected
Fig. 1/4: Connecting the screening
1
2
1. Installation
CP-FB13-E 9904b
1-15