2.3.3 Sending configuration data
The configuration data are transferred from the DP
master to the CP system with the function
Chk_Cfg.
PLEASE NOTE
The configuration of a valve terminal must be carried
out as follows:
– per string:
one DP identifier for inputs and outputs
– via sum identifier:
sum of the input bytes and sum of the output bytes
The structure of the identifier byte can be found in sec-
tion 2.1.4.
Parameter summary (Chk_Cfg)
Octet 1-n:
DP Identifier
Permitted identifiers for Festo CP systems
in compact mode (see also Fig. 2/5):
No. of I/Os
Inputs
decimal
Outputs
decimal
up to 16
017
033
up to 32
019
035
up to 48
021
037
up to 64
023
039
2. Commissioning
CP FB13-E 9904b
2-35
Summary of Contents for Compact Performance CP-FB9-E
Page 12: ...Chapter 1 Installation 1 Installation CP FB13 E 9904b 1 1 ...
Page 30: ...Chapter 2 Commissioning 2 Commissioning CP FB13 E 9904b 2 1 ...
Page 70: ...Chapter 3 Diagnosis 3 Diagnosis CP FB13 E 9904b 3 1 ...
Page 95: ...3 Diagnosis 3 26 CP FB13 E 9904b ...
Page 96: ...Appendix A Technical specifications A Technical specifications and index CP FB13 E 9904b A 1 ...