LED designation
Function
Meaning
BUS ERROR
PROFIBUS communication
Blinks if there is an error in
connection with the fieldbus
POWER
Operating voltage display
of internal electronic components
Lights up if operating voltage
is applied to pin 1
and the node
is ready for use
POWER V
Operating voltage display
of valves
Lights up if operating
voltage of valves
is ok (pin 2);
blinks if operating voltage
is < 20.4 V
0..3
CP string LED
During start-up phase:
blinks if the string assignment
has been changed since
the last operation
during operation:
lights up if a CP connection
has been interrupted
3.1.1 Normal operating status
In normal operating status the following LEDs light up
on CP node 13:
( = lights up;
= LED flashes; = out)
LEDs
Operating status
Error treatment
BUS
POWER
POWER V
normal
none
3. Diagnosis
3-4
CP FB13-E 9904b
Summary of Contents for Compact Performance CP-FB9-E
Page 12: ...Chapter 1 Installation 1 Installation CP FB13 E 9904b 1 1 ...
Page 30: ...Chapter 2 Commissioning 2 Commissioning CP FB13 E 9904b 2 1 ...
Page 70: ...Chapter 3 Diagnosis 3 Diagnosis CP FB13 E 9904b 3 1 ...
Page 95: ...3 Diagnosis 3 26 CP FB13 E 9904b ...
Page 96: ...Appendix A Technical specifications A Technical specifications and index CP FB13 E 9904b A 1 ...