A.1 Technical specifications of fieldbus node CP FB13-E
General
Temperature range:
– operation
– storage/transport
- 5
o
C ... + 50
o
C
-20
o
C ... + 70
o
C
Relative humidity
95 %, non condensing
Protective class as per EN 60 529
Plug connectors inserted or fitted with
protective caps
IP 65
Protection against electric shock
(protection against direct and indirect
contact as per EN 60204-1/IEC 204)
By means of PELV power units
(protected extra low voltage)
Operating voltage
of electronic components and input modules
Pin 1
Operating voltage connection
– rated value
– tolerance
24 V DC
20.4 .. 26.4 V
Current consumption
– pin 1 node FB13-E
– all electronic components in CP system
250 mA
see manual "CP system",
chapter 3.1.2, Table of current consumption
Residual ripple
4 Vpp (within tolerance)
Power failure bridging time
20 ms
A. Technical specifications and index
CP FB13-E 9904b
A-3