CPX-FVDA-P2
32
Festo – CPX-FVDA-P2-Z6 – 2018-02a English
1
Safety instructions
Warning
Nonobservance of safety regulations can result in death, serious injuries or major
material damage.
Always follow the safety instructions.
Note
Electronics modules include electrostatically sensitive devices.
Incorrect handling can cause damage to the electronics modules.
Observe the handling specifications for electrostatically sensitive devices.
Discharge static electricity from your body before assembling or disassembling
modules to protect the modules.
Note
To ensure compliance with the intended use:
Each output channel that is in use must be switched at least once a week.
If test pulses are switched off:
Each output that is in use must be switched at least once a day.
Note
To ensure compliance with the safety level:
Each output channel that is in use must be switched on for more than 1 minute at
least once every 8 operating hours.
The operating time begins when the output module is first switched on.
Note
Use a maximum of 2 output channels in a common safety pilot circuit.
Observe the regulations for providing voltage (protective extra-low voltage, PELV)
to CPX terminals in the CPX system description P.BECPXSYS….