Festo KBS-FEC FC30- 0206NH English
36
Digital outputs
Number
8 consisting of:
2 relay outputs
6 transistor outputs
Switchable voltages / currents
Transistor outputs
+24 V DC +20 %/-15 %;
nominal current / output 0.6 A
resistant to short-circuit / over-
load; lamp load: max. 5 W;
operating frequency: max. 1 kHz
Switchable voltages / currents
Relay outputs
5 A/250 V AC, 5 A/30 V DC;
minimum load: 10 mA at 5 V DC;
operating frequency: max. 25 Hz
Current / loading
– no current
– 0,2 A
– 1 A
– 2 A
Ohm
resistive load
inductive load
20 Mio. cycles
20 Mio. cycles
1 Mio cycles
800.000 cycles
500.000 cycles 300.000 cycles
300.000 cycles 100.000 cycles
Electrical isolation
yes, optocoupler
Electrical isolation between
groups
one group with 2 relays
one group with 6 transistor out-
puts
Permitted length of connecting
cables
max. 30 m
Maximum group current
3.2 A; for transistor outputs