MS6−SFE−...
Festo MS6−SFE−... 0507NH English
53
10
Troubleshooting
Fault
Possible cause
Remedy
Incorrect measured
value display
MS6−SFE−... operated with
non−permitted medium
Operate the MS6−SFE−... only
with permitted medium
Sieve cartridge with type
MS6−SFE−F5−... dirty
Clean the sieve cartridge
Incorrect flow direction
Operate the MS6−SFE−... in
flow direction from 1 to 2
MS6−SFE−... very dirty
Return MS6−SFE−... to Festo
Display shows
Er01"
Sieve cartridge or starting
stretch missing
Operate the MS6−SFE−... with
sieve cartridge or starting
stretch
With flow
measurement:
Measured value is
displayed flashing
Measurement outside
permitted measuring range
Accuracy refers only to the
permitted measuring range
With consumption
measurement:
Measured value is
displayed flashing
Measuring range end value is
exceeded at least once.
Specified accuracy cannot
therefore be maintained.
Make sure that the measuring
range end value is not
exceeded
Outputs do not
switch according to
setting.
Short circuit/overload at
relevant output
Eliminate short circuit/
overload
Settings cannot be
edited (Lock)
Access protection active
Enter the security code
Fig.17