SDE1−...
Festo SDE1−... 0511e English
43
Electrical installation
Warning
S
Use only power units which guarantee reliable electrical isolation of the
operating voltage as per IEC/DIN EN 60204−1. Observe also the general
requirements for PELV power circuits as per IEC/DIN EN 60204−1.
Please note
Long signal cables reduce the immunity to interference.
S
Make sure that the signal cable is not longer than 30 m.
S
Connect the SDE1−... as follows:
SDE1−...−P1/N1 (1 output)
Pin / cable colours
1)
Assignment
Plug
2)
3−pin M8
4−pin M12
1 / brown (BN)
+24 V DC power supply
3−pin M8
4 / black (BK)
Output A (Out A)
3 / blue (BU)
0 V
4−pin M12
2 /
n.c.
1)
Using the connection socket with cable as specified in the chapter Accessories"
2)
Tightening torque: M8 plug max. 0.3 Nm; M12 plug max. 0.5 Nm
Fig.8
Summary of Contents for SDE1 Series
Page 30: ...SDE1 Festo SDE1 0511e Deutsch 30 Bild 23 EDIT Modus ...
Page 32: ...SDE1 Festo SDE1 0511e Deutsch 32 Bild 24 TEACH Modus ...
Page 60: ...SDE1 Festo SDE1 0511e English 60 Fig 23 EDIT mode ...
Page 62: ...SDE1 Festo SDE1 0511e English 62 Fig 24 TEACH mode ...
Page 63: ...SDE1 Festo SDE1 0511e 63 de Lochbilder Adapterplatte en Hole pattern on adapter plate ...