5. Diagnosis and error treatment
5-3
Festo P.BE-SPC11-SYS-ASI-EN en 0203NH
5.1
On-the-spot diagnosis
If a fault occurs, the SPC11 will display a fault number and
react as follows:
– The valve slide of the proportional directional control
valve will then be brought into the electrical mid-position
(flow blocked).
– The ASI LED or the fault LED lights up or flashes.
– No new positioning task will be accepted.
– Depending on the operating mode used, the fault will be
sent to the AS-Interface master (see section 5.2).
In order to quit the error after eliminating it:
S
With communication profile “Standard slave with:
4-bits I/O data:” Switch the operating voltage off and
then on again (black AS-Interface cable).
S
With communication profile “Slave profile 7.4:”
Switch the operating voltage off and then on again (black
AS-Interface cable) or quit the fault with the aid of the bit
“Quit Error” in the order byte.
Summary of Contents for Soft Stop SPC11 Series
Page 2: ......
Page 14: ...Contents and general instructions XII Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 15: ...Summary of components 1 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 1 ...
Page 25: ...Fitting 2 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 2 ...
Page 28: ...2 Fitting 2 4 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 29: ...Installation 3 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 3 ...
Page 61: ...Commissioning 4 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 4 ...
Page 100: ...4 Commissioning 4 40 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 101: ...Diagnosis and error treatment 5 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 5 ...
Page 114: ...5 Diagnosis and error treatment 5 14 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 127: ...Technical appendix B 1 Festo P BE SPC11 SYS ASI EN en 0203NH Appendix B ...