3. Installation
3-21
Festo P.BE-SPC11-SYS-ASI-EN en 0203NH
3.3.2 Assigning the AS-Interface slave addresses
Warning
Undesired movements of the connected actuators can
cause injury to human beings or damage to property.
Before setting the AS-Interface address, switch off the
operating voltage and the compressed air supply either
simultaneously or in the following sequence:
1. the compressed air supply
2. the operating voltage.
Please note
The voltage required for the addressing is supplied by the
addressing device.
Recommendation: Use addressing device type ASI-PRG-ADR
from Festo with adapter cable.
Before connecting the SPC11 to the AS-Interface bus and the
power supply, assign an unused AS-interface address to each
slave. Set the desired address with the AS-interface addres-
sing device. The SPC11 is an AS-Interface standard slave.
Permittted addressing range 1...31. Please note:
– Factory setting: Address 00
– ID code: 4
– I/O code: 7
H
:
D0: I/O (I1/O1)
D1: I/O (I2/O2)
D2: I/O (I3/O3)
D3: I/O (I4/O4)
– Auto programming is not supported.
Summary of Contents for Soft Stop SPC11 Series
Page 2: ......
Page 14: ...Contents and general instructions XII Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 15: ...Summary of components 1 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 1 ...
Page 25: ...Fitting 2 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 2 ...
Page 28: ...2 Fitting 2 4 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 29: ...Installation 3 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 3 ...
Page 61: ...Commissioning 4 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 4 ...
Page 100: ...4 Commissioning 4 40 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 101: ...Diagnosis and error treatment 5 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 5 ...
Page 114: ...5 Diagnosis and error treatment 5 14 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 127: ...Technical appendix B 1 Festo P BE SPC11 SYS ASI EN en 0203NH Appendix B ...