3. Installation
3-25
Festo P.BE-SPC11-SYS-ASI-EN en 0203NH
3.3.4 Connecting the operating voltage and the AS-Interface bus
Recommendation: In order to connect the load voltage cable
and the AS-Interface bus cable use the following accessories
from Festo:
Accessories
Type designation
AS-Interface combi power pack
ASI-CNT-115/230VAC
AS-Interface bus cable (yellow)
KASI-1.5-Y-100
Additional supply cable (black)
KASI-1.5-Z-100
AS-Interface cable cap
ASI-KK-FK
AS-Interface cable socket
ASI-SD-FK or ASI-SD-FK180
Addressing device
ASI-PRG-ADR
Identification labels
ISB6x10
Installation instructions
Caution
In order to avoid interference caused by electromagnetic
influences:
S
Connect the earth connection on the left-hand side of the
housing with low impedance (short cable with large
cross-sectional area) to the earth potential.
S
Connect a protective conductor with sufficient cross
sectional area to the drive, if this is not mounted on an
earthed machine stand.
Summary of Contents for Soft Stop SPC11 Series
Page 2: ......
Page 14: ...Contents and general instructions XII Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 15: ...Summary of components 1 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 1 ...
Page 25: ...Fitting 2 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 2 ...
Page 28: ...2 Fitting 2 4 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 29: ...Installation 3 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 3 ...
Page 61: ...Commissioning 4 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 4 ...
Page 100: ...4 Commissioning 4 40 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 101: ...Diagnosis and error treatment 5 1 Festo P BE SPC11 SYS ASI EN en 0203NH Chapter 5 ...
Page 114: ...5 Diagnosis and error treatment 5 14 Festo P BE SPC11 SYS ASI EN en 0203NH ...
Page 127: ...Technical appendix B 1 Festo P BE SPC11 SYS ASI EN en 0203NH Appendix B ...