8
Remove SET
LEVEL CAP.
With machine running,
reset switch.
Tripped ?
Tripped ?
Is an increase in
sensitivity required ?
Switch is set.
Retract SET LEVEL SCREW
steadily until tripped, then
advance 1/2 turn.
Y
Y
Y
N
N
N
Advance SET LEVEL SCREW
steadily 1/2 turn.
Reset switch.
Reset Machine.
5. Set-up Sequence
No adjustment is needed if the vibration switch has been ordered preset for your application.
Otherwise, the vibration switch is factory set accurately to 3g. For set up in the field, adjust SET
LEVEL so that the switch no longer trips in normal running with reasonable sensitivity to
excesssive vibration as follows: