Talentum UV/IR Test Unit Procedure
0044-112-01
Introduction
This note explains:
•
The purpose of the modification provided by the Talentum UV/IR Adaptor
•
The procedure for modifying the Talentum Test Unit to incorporate the Talentum UV/IR Adaptor
•
How to test a Detector using the Test Unit
Test Unit with Talentum UV/IR Adaptor
The Talentum Test Unit is designed to assist with performing a
“
flame
”
test without the need of a live
flame.
We have developed the Talentum UV/IR Adapter to optimise the output of the Test Unit for testing
Talentum UV/IR flame detectors only.
We strongly recommend that Test Units are modified with the adapter whenever used to test
UV/IR flame detectors, because without the modification the torch is less likely to identify a
performance issue with the flame detector.
Flame detectors for which this Test Unit is suitable:
16591 UV/IR2 Flame Detector
16521 UV/IR2 Flame Detector - Flameproof (Exd)
16531 UV/IR2 Flame Detector - Stainless Steel
16561 UV/IR2 Flame Detector - Stainless Steel, Flameproof (Exd)
The adapter works by changing the filter arrangement on the Test Unit so that it is optimised for testing
UV/IR flame detectors. Modifying the Test Unit with the adapter changes the output IR and UV
spectrum, so it closely matches a yellow flame. This subjects the Talentum detector to a test more suited
to identifying a performance issue. The output of the torch without this modification matches a blue
flame.
Health and Safety
In accordance with the Talentum User Guide, users should conduct regular maintenance and testing of
Talentum fire detection products according to the risk and environment in which the product(s) are
located. The frequency of such maintenance and test schedule should be revisited at regular intervals
to ensure that it remains appropriate.
The Talentum Test Unit is designed to assist with performing a “flame” test without the need of a live
flame. Adding our Talentum UV/IR Adapter ensures the output of the Test Unit is optimised for testing
UV/IR flame detectors.
Please note that the Test Unit does not have an (Ex) approval for hazardous areas. A permit is required
to test a detector in such areas. Alternatively, the detector should be removed and placed within a safe
location to perform the test.
Testing of a flame detector should only be conducted where it is safe to do so and by personnel with
appropriate training and equipment.