background image

Talentum UV/IR Test Unit Procedure 

 

 

 

0044-112-01 

Introduction 

This note explains:  

 

The purpose of the modification provided by the Talentum UV/IR Adaptor 

 

The procedure for modifying the Talentum Test Unit to incorporate the Talentum UV/IR Adaptor 

 

How to test a Detector using the Test Unit 

Test Unit with Talentum UV/IR Adaptor  

The Talentum Test Unit is designed to assist with performing a 

flame

 test without the need of a live 

flame.  

We have developed the Talentum UV/IR Adapter to optimise the output of the Test Unit for testing 
Talentum UV/IR flame detectors only.  

We strongly recommend that Test Units are modified with the adapter whenever used to  test 
UV/IR  flame  detectors,  because  without  the  modification  the  torch  is  less  likely  to  identify  a 
performance issue with the flame detector.

   

Flame detectors for which this Test Unit is suitable: 

16591 UV/IR2 Flame Detector  
16521 UV/IR2 Flame Detector - Flameproof (Exd) 
16531 UV/IR2 Flame Detector - Stainless Steel 
16561 UV/IR2 Flame Detector - Stainless Steel, Flameproof (Exd) 
 
The adapter works by changing the filter arrangement on the Test Unit so that it is optimised for testing 
UV/IR  flame  detectors.  Modifying  the  Test  Unit  with  the  adapter  changes  the  output  IR  and  UV 
spectrum, so it closely matches a yellow flame. This subjects the Talentum detector to a test more suited 
to identifying a performance issue. The output of the torch without this modification matches a blue 
flame. 

Health and Safety 

In accordance with the Talentum User Guide, users should conduct regular maintenance and testing of 
Talentum  fire  detection products  according  to  the  risk  and  environment  in  which  the product(s)  are 
located. The frequency of such maintenance and test schedule should be revisited at regular intervals 
to ensure that it remains appropriate.  

The Talentum Test Unit is designed to assist with performing a “flame” test without the need of a live 

flame. Adding our Talentum UV/IR Adapter ensures the output of the Test Unit is optimised for testing 
UV/IR flame detectors. 

Please note that the Test Unit does not have an (Ex) approval for hazardous areas. A permit is required 
to test a detector in such areas. Alternatively, the detector should be removed and placed within a safe 
location to perform the test.  

Testing of a flame detector should only be conducted where it is safe to do so and by personnel with 
appropriate training and equipment.  

Summary of Contents for Talentum UV/IR Test Unit

Page 1: ...t so that it is optimised for testing UV IR flame detectors Modifying the Test Unit with the adapter changes the output IR and UV spectrum so it closely matches a yellow flame This subjects the Talentum detector to a test more suited to identifying a performance issue The output of the torch without this modification matches a blue flame Health and Safety In accordance with the Talentum User Guide...

Page 2: ...he front of the torch including the four screws and washers and put them aside 3 Fit the modification assembly so that the seven optical filters are positioned over the test torch bulb and the UV source sits above the test torch on the keypad side as shown below 4 Take the new filter arrangement and without removing any parts use the four new screws to locate it on the front of the Test Unit Gentl...

Page 3: ...orming the test and that its bulb is working correctly If the Test Unit is insufficiently charged or the bulb has failed it is likely to result in test failure no response from the detector If testing a UV version of Talentum turn on the UV lamp using the switch at the back of the UV lamp unit A green LED will indicate that the UV lamp unit is on Hold the Test Unit as still as possible at a distan...

Page 4: ...nager for support Summary Test description Flame dimensions Distance to detector Test Unit with UV IR Adapter N A 50 70cm 1 2 ft Warranty Warranty is not affected by using these components with the test unit provided that no other modifications are implemented The test unit should still be serviced and maintained in accordance with the instructions The new free issue components carry a limited 1 y...

Reviews: