21689_r03
7/13
In the third step you select the ending time. The final time
can not be less than initial time, selecting two coincident
values for initial time and final time, the daily schedule is
not changed.
The last item on the “Programming” menu allows you to
copy the program day to another day.
At the top you select the source day in the lower you select
the destination day, You can also copy a program of the
day all week and have the same program every day, to do
this select as target the "ALL".
When you press OK, a message confirms your copy of the
program.
Completed the description of the "Programming menu”, we
return to describe the sub menu "SETTING MENU".
The “Time setting” submenu on the "SETTING MENU"
allows adjustment of the current time and day of the week.
Pushing the
↓
and
↑
buttons you select the item you want to
change, while pushing the + and - buttons you change the
value.
Pushing the OK button, you confirm the changes.
The “Language” submenu on the "SETTING MENU" allows
set the language of texts on the chronothermostat.
As seen above, this setting is required when you first start
or after a reset of the chronothermostat, then it can be
changed at will.
The last item, “Heating Control” of the "SETTING MENU",
concerns the method used by the chrothermostat for
controlling room temperature.
It is a regulation that requires a specific knowledge of the
heating system installed and is reserved, therefore, for
advanced users: make changes without knowledge of the
techniques of temperature control is not recommended.
The chronothermostat allows you to choose among four
methods of temperature control environment:
•
Proporzional
•
On/Off
•
Outside temperature compensation
•
Outside temperature compensation with mix
Proporzional
Selecting proportional mode, the temperature setpoint of
the system is modulated depending of the difference
between the set room temperature and measured room
temperature.
The setpoint of circuit heating, in this case, it will be
proportional to the difference of these two temperatures
according to the following rule:
if
T
a
≤
T
ap
- 1 + offset
then
T
i
= max
if
T
ap
– 1 + offset < T
a
< T
ap
+ 1 + offset
then
T
i
= ( max / 2 ) x ( T
ap
– T
a
+ 1 + offset)
if
T
a
≥
T
ap
+ 1 + offset
then
T
i
= 0
when
T
i
circuit heating setpoint.
T
ap
room temperature setpoint.
T
a
room temperature measured
offset
correction
value (settable),
max
maximum circuit heating setpoint (set by the
user).
Is defined, in practice, a proportional band of width 2 º C
between the temperatures.
T
ap
- 1 + offset
(which corresponds
T
i
= max
),
T
ap
+ 1 + offset
(which corresponds
T
i
= 0
)
and centered in
T
ap
+ offset
.
The offset, is set from 0 to 1 ° C, the offset cent ers the
band so that in correspondence of
Ta = Tap
, you obtain the
setpoint of circuit heating desideratum.
With the default offset = 0, the band has a width of 2 º C
and is centered in
Tap
.