Function
Value
Maximum primary circuit temperature
80 °C
Circulator lock prevention operation time
10 sec
Circulator lock prevention activation time
24 hours
Anti-freeze temperature On (circulator only)
< 8 °C
Anti-freeze Temperature On (circulator and power)
< 5 °C
Anti-freeze Temperature Off
> 20 °C
SETPOINTS AND PARAMETERS
Function
Default
Range
Central heating setpoint
60 °C
30 - 75 °C
Underfloor central heating setpoint
30 °C
10 - 40 °C
Room setpoint (with external probe present)
20 °C
10 - 30 °C
PARAMETERS
Function
Display
Def. Range
External probe enable (SE)
idx: 001
0
0 - 1
Building dispersion coefficient
idx: 002
35
5 - 35 °C
Central heating post-circulation duration
idx: 004
30
1 - 180 sec
Primary exchanger ON delay
idx: 005
0
0 - 240 sec
Min. temperature of primary exchanger for
circulator ON
idx: 006
30
0 - 50 °C
Type of sanitary water storage tank
idx: 008
0
0 = internal with probe
1 = external with
thermostat
2 = external with probe
PWM circulator operation speed
idx: 010
4
1 = 400 l/h
2 = 800 l/h
3 = 1,000 l/h
4 = 1,200 l/h
Boiler power selection
idx: 011
3
1 - 4
System pressure sensor type
idx: 012
1
0 - 2
Value
idx:
011
Total
power
[kW]
No.
TRIAC
No. of heating elements
used and power of each
element
G1
[kW]
G2
[kW]
G3
[kW]
G4
[kW]
G5
[kW]
002
6
5
no. 2 heating elements,
power 3 x 1kW
2
1
1
2
2
002
8
5
no. 1 heating elements,
power 3 x 1kW
no. 1 heating elements,
power 3 x 2kW
2
2
2
2
2
002
9
5
no. 1 heating elements,
power 3 x 1kW
no. 1 heating elements,
power 3 x 2kW
3
2
2
2
2
003
12
5
no. 2 heating elements,
power 3 x 2kW
4
2
4
2
2
004
18
5
no. 3 heating elements,
power 3 x 2kW
6
4
6
2
2