background image

TECHNICAL SPECIFICATIONS 

 

General features 
Type 

Line-Interactive 

Power capacity 

1000VA / 600W 

Output Power Factor 

0.60 

Input 
Input Voltage Range 

165-290 VAC 

Frequency (Synchronized Range) 

+/- 5Hz / 50Hz or 60Hz 

Output 
Nominal Output Voltage 

230 VAC 

Pure Sine Wave 

Yes 

THDv 

≤3% Full Linear Load; ≤5% Non-Linear Load 

Voltage Regulation (Bat. Mod.) 

±10% 

Frequency (Battery Mode) 

±0,5 Hz 

Technical details 
Transfer Time [AC to Battery] 

5ms typical / <10ms max. 

Charger 

1A 

Protection 

Overload protection on utility: fuse; on battery: 
internal current limiting 

Efficiency 
LINE mode full Load 

95.0% 

Batteries and autonomy time 
Batteries 

4x 6V /7 Ah 

DC Voltage 

24 V 

Recharge Time 

8h to 90% 

Connections and communication 
IEC 320 C13 Outlet 

Input 

IEC 320 C14 

Software 

Power Master   

USB port & HID Support 

Yes 

RS-232 Port & Extension Slot 

Yes 

EPO Port 

Yes 

Environment 
Noise Level 

No Fan /    <40dB 

Temperature & Humidity 

0°C – 40°C / 0% - 90% RH (non-condensing) 

Dimentions 
Width x Height x Depth 

433 x 44 x 389 mm 

Weight 

14.2 kg 

 

 

Summary of Contents for KI 1000R 1U

Page 1: ...KI 1000R 1U 1000VA Line Interactive Sinewave UPS Version USER MANUAL ...

Page 2: ...EM UNPACKING The box should contain the following 1 UPS Unit 1 2 User Manual 1 HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 1 Ensure that the equipment plugged into the battery power supplied outlets does not exceed the UPS unit s rated capacity If rated unit capacities are exceeded an overload condition may occur and cause the UPS unit to shut down or the fuse blow 2 There are many f...

Page 3: ...For extended storage in moderate climates the battery should be charged for 12 hours every 3 months by plugging the power cord into the wall receptacle and turning on the main switch Repeat it every 2 months in high temperature locations BASIC OPERATION FRONT AND TOP PANEL DESCRIPTION 1000 1500 R1U 1 AC Inlet Connect to utility power through the input power cord 2 Input Circuit Fuse The fuse provi...

Page 4: ...the UPS ON or OFF 10 Mute Button The audible alarm can be turned off on by pressing this button SOFTWARE DOWNLOAD Power Master management software provides a user friendly interface for your power systems The graphic user interface is intuitive and displays essential power information at a glance Please follow procedure below to install the software Installation procedure 1 Download Power Master f...

Page 5: ...ansfer Time AC to Battery 5ms typical 10ms max Charger 1A Protection Overload protection on utility fuse on battery internal current limiting Efficiency LINE mode full Load 95 0 Batteries and autonomy time Batteries 4x 6V 7 Ah DC Voltage 24 V Recharge Time 8h to 90 Connections and communication IEC 320 C13 Outlet 4 Input IEC 320 C14 Software Power Master USB port HID Support Yes RS 232 Port Extens...

Page 6: ...DEFINITIONS FOR ILLUMINATED LCD INDICATORS LCD indication Line Battery Mode ALARM DEFINITIONS ...

Page 7: ...TROUBLE SHOOTING ...

Page 8: ...UPS REAL VIEW Front view Back view ...