MY Series (10kVA-40kVA) UPS
User Manual
A Technical Specifications
97
A
Technical Specifications
Model
Index
MY10/10
S
MY15/15
S
MY20/20
S
MY30/30
S
MY40/40
S
Input
Input mode
1W+ N+PE (can be set to 3W + N +
PE)
3W + N + PE
Voltage range (Vac)
When the input voltage in the range of 176
~
280, the UPS can
bear load of 100% rated power;
When the input voltage in the range of 80-176, the output of
the UPS needs to decrease rated power linearly to use.
Frequency range (Hz)
40~70
Bypass synchronism track
range (Hz)
50/60±10% (50/60 self-adaption)
Bypass input voltage
range (Vac)
220/230/240±20% (phase voltage) (default is 220)
Input power factor
≥
0.99
Input THDI
Resistive full load:
≤
3%; non-linear full load:
≤
5%
Battery voltage (Vdc)
MY15/15S~40/40S:
±
144 ~
±
240 (can be selected from
±
72 cells ~
±
120 cells, default is
±
96 cells, when the battery
voltage is set from
±
72 cells ~
±
90 cells, the output of the
UPS decreases to 75% rated) (single battery voltage is 2Vdc);
MY10/10S:
±
96 ~
±
240 (can be selected from
±
48 cells ~
±
120 cells, default is
±
48 cells.