5 Touch Screen Operation
MY Series (10kVA-40kVA) UPS
User Manual
70
Figure5-26
System management page 3 of ECO set
Table5-1
Setting description for system mange
Item
Settable value
Output voltage (V)
220V,230V,240V
Output frequency (Hz)
50Hz,60Hz
Output voltage adjustment (V)
-5~+5
Max. bypass voltage (%)
10%,15%,20%
Min. bypass voltage (%)
10%,15%,20%
Bypass frequency range (%)
5%,10%
ECO mode
On, Off
ECO voltage range (%)
10%,15%
ECO frequency range (%)
5%,10%
After changing the parameter, it is necessary to click "
" button to save the setting. If the
setting is successful, there will be a "
" icon at the right side of the parameter, as shown in
Figure5-27, if the setting is unsuccessful, there will be a "
" icon at the right side of the parameter,
as shown in Figure5-28.