COMBUSTION AIR SYSTEM  

Model: CAS-3 

 

 

 

 

 

 

 

 

 

 

 

This product is designed for use with any oil burning furnace, water heater, or 
boiler with 120 VAC control systems. It may also be used with more than one 
appliance. The CAS unit mechanically draws air into a structure and 
disperses it near the combustion air intake of an appliance. If an optional 
Vacuum Relief Valve (VRV) is used, the incoming air is tempered before 
entering the structure's airspace. Refer to Diagram A and B for guidance in 
setting up the CAS system based on the size and length of the connecting 
duct-work and the input rating of the appliance.

 

 

This device MUST be installed by a qualified agency in accordance with the manufacturers installation 
instructions.

  

The definition of a qualified agency is: 

any individual, firm, corporation or company which either in person or through a 

representative is engaged in, and is responsible for, the installation and operation of gas appliances, who is experienced 
in such work, familiar with all the precautions required, and has complied with the requirements of the authority having 
jurisdiction.

 

 

 

DO NOT DESTROY 

THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT 

 

 

 

I

TEMS INCLUDED IN KIT

:

 

1) Motorized 

Blower 

1) 

4" galvanized intake air Vent Hood 

2) 

Mounting brackets to secure the CAS to a wall 

2) Wire/conduit 

connector(s) 

1) 

4" x 6" Pipe Increaser Fitting 

1)  

6" Orifice Ring 

1) Instruction 

Sheet 

1) 

High/Low Motor Speed Switch 

Summary of Contents for 46261200

Page 1: ...t work and the input rating of the appliance This device MUST be installed by a qualified agency in accordance with the manufacturers installation instructions The definition of a qualified agency is...

Page 2: ...ould be used when installing the CAS system Using these charts will help ensure that the proper amount of air is drawn into the structure as needed by the appliance The defined regions shown correspon...

Page 3: ...ry is the diagonal line that says 4 inch Duct Hood Orifice Ring Therefore place the Orifice Ring into the inlet on the CAS so that it sits on the ledge above the fan It does not matter which way the O...

Page 4: ...FIRING RATE gallons per hour 1 gallon oil hr 140 000 BTU hr 6 Duct Hood 4 Duct Hood 4 Duct Hood Orifice Diagram A LOW SPEED SIZING CHART 0 50 100 150 200 250 300 0 50 100 150 200 250 300 350 400 GAS I...

Page 5: ...moving during operation INTAKE AIR HOOD LOCATION The 4 galvanized vent hood should be located on an outside wall maintaining minimum clearances to other intake and exhaust vents in accordance with the...

Page 6: ...terminals Use the enclosed conduit connector s to route the appropriate wires through the CAS housing The incoming ground wire must be attached to the green colored ground screw near the wire termina...

Page 7: ...Page 7 Figure 6 Riello Oil Fired System Figure 7 Single Vent Oil Fired System...

Page 8: ...Page 8 Figure 8 Chimney Vent Two Oil Fired System with CAC 120...

Page 9: ...4 Clear any obstructions if present from the inlet of the vent hood and the outlet of the CAS unit 5 Periodically the fan blade chamber may need cleaning First disconnect the power supply to the CAS...

Page 10: ...t must be disassembled If this is necessary take note of the positions and locations of whatever items that may need to be removed to replace other items If in doubt please consult the Field Controls...

Page 11: ...Page 11 NOTES...

Page 12: ...Page 12 PN 46261200 Rev I 10 06...

Reviews: