SPECIAL VENTING APPLICATION 

INSTALLATION SHEET FOR

 

AQUAHUT

® 

WATER HEATER ENCLOSURES

 

 

This sheet covers the requirements for installing the Star-Kap™ on an 

Aquahut

®

 gas water heater 

enclosure. The 

Aquahut

®

 enclosure is designed for the purpose of housing a gas water heater 

outside of the living space of a structure. These requirements are based on the A.G.A. test reports 
C-FT-5-90, C-FT-8-90, FT-C-12-93, FT-C-13-93, FT-C-14-92 and the SBCCI letter dated May 24, 
1990. The 

Aquahut

®

 water heater enclosure is not sold or manufactured by the Field Controls Co. 

These installation instructions only address the installation of the Star-Kap™, state the maximum 
capacity water heater allowed in an 

Aquahut

®

 and the vent termination clearances from windows or 

openings into a building structure as tested in the A.G.A. field reports C-FT-5-90, C-FT-8-90, FT-C-
12-93, FT-C-13-93, FT-C-14-92 and the SBCCI letter dated May 24, 1990. 
 

INSTALLATION GUIDE LINES 

1.  The maximum gas water heater appliance to be operated in a 

Aquahut

®

 enclosure: up to 90,000 

BTU/HR input. 

2.  Two (2) make up/combustion air openings into the 

Aquahut

®

 enclosure shall be installed. Each 

opening size shall be based on one (1) square inch per 4000 BTU/HR. The vent termination shall 
have the following clearance distances. 

a.  AH40 Model 

Aquahut

®

 

14” from combustible exterior wall to center of vent cap 

b.  AH50 Model 

Aquahut

®

 

16” from combustible exterior wall to center of vent cap 

c.  A minimum of 12” from any window or opening into the main building structure  
d.  A minimum of 18” below an eave or overhang 

 

STAR-KAP™ INSTALLATION 

1.  Before installation, apply two (2) beads of high 

temperature silicone sealant or equivalent around 
the bottom of the storm collar and one (1) inch 
above the end of the Star-Kap™ body. (See 
Figure 1) 

2.  Insert the Star-Kap™ into the inside of the single 

wall vent pipe, making sure the Star-Kap™ is 
seated against the storm collar. Fasten the Star-
Kap™ to the single wall vent pipe, by using 
three (3) sheet metal screws. Placement of the 
screws should be approximately 1/2 inch from 
the end of the single wall vent pipe. The heads 
of the screws should be covered with high 
temperature silicone or equivalent. 

Figure 1

 

P/N 46263400 Rev D 11/00