background image

 

Page 7

AIR FLOW ADJUSTMENTS 

In order to obtain proper system draft, the power venter has an airflow adjustment damper built-in. 
(See Figure 12) This damper should be used to make coarse draft adjustments while the barometric 
should be used for finer adjustments. Changes in the adjustment of the 4" MG-1 Draft Control should 
be made by adding or removing the washer-like weights (supplied with the control) to or from the 
weight holder chain assembly. After the control is adjusted, its action will be entirely automatic, the 
gate will open or close by itself to correct for changes in the draft. The control MUST be adjusted to 
the desired draft setting by adding or removing the washer-type weights supported by the two chains 
on the side of the draft control. (See Figure 13) 

DO NOT 

move the weight attached directly to the 

gate, this is used only for balancing at the factory.

 

R

EFER TO THE FOLLOWING TO PROPERLY SET THE AIRFLOW ADJUSTMENTS ON THE 

P

OWER 

V

ENTER AND 

D

RAFT 

C

ONTROL

 

1.  Set the adjustment damper in the SWG venter to its full open position. 
2.  Start with no weights on the chain hanger of the MG-1 draft control. 
3.  Follow the appliance manufacturer's procedures for starting the heating 

appliance. Then adjust the thermostat to call for "Heat". 

4.  After the system has operated for at least 10 minutes to stabilize flue gas 

temperatures, check for negative draft or up-draft at the heating appliance 
outlet. Use a draft gauge, velocity meter or match test procedure. 

5.  Loosen the damper locking screw on the underside of the SWG outer pipe 

and rotate the adjustment damper closed to obtain the minimum air flow 
required to maintain draft. Then increase air flow slightly (10% over minimum 
air flow rate) to ensure proper venting. If using a draft gauge, draft settings 
should typically be -0.02" of water column draft at the appliance outlet. (Check equipment requirement.) 

6.  Observe the position of the gate on the draft control. It should be set so that during normal operation the gate is in the 

midpoint of its swing. This will be approximately 30°-45° from vertical. 

7.  When first setting up the system the gate on the control will probably be fully open. Add washer weights to the chain 

hanger until the gate stabilizes at the midpoint of its swing. 

8.  Changing the weight on the draft control will affect the system draft, therefore repeat steps 5 through 7 as necessary 

until proper draft is obtained and the draft control gate is in the proper position. 

9.  Tighten the damper locking screw on the SWG to prevent it from moving during operation and secure the washer 

weights on the draft control with the provided screw and nut. 

W

HILE ADJUSTING THE SYSTEM AIRFLOW

TWO THINGS ARE ESSENTIAL

 

1.  The appliance burner must operate for at least 10 minutes prior to setting the draft to stabilize flue gas temperatures. 
2.  An analysis of the flue gases is necessary to determine the percentage of CO

2

 and check for the presence of CO. 

Refer to the local gas company for the proper CO

2

 readings and allowable CO levels. 

Refer to the General Installation Inspection section to check for negative pressure problems in the building. If sufficient 
combustion air for the burner is not provided, a flow reversal during the off cycle could occur within the venting system. 
This may cause combustion problems as well as condensation that could block the air pressure sensing tube. It may also 
contribute to premature motor failure. Combustion, and/or make-up air, should be supplied from outside the structure and 
the air inlet should be on the same wall as the power venter discharge. For example, tightly constructed homes and 
homes retro-fitted from electric heated systems are more likely to experience combustion and/or make-up air problems. 
For further information consult Form #4199, "The Field Report - Effects of Insufficient Combustion Air" available from The 
Field Controls Company. 

PROVING SWITCH ADJUSTMENTS

 

Refer to the following for air pressure switch adjustment procedure and system 
checkout procedures before operating the appliance continuously. 
After proper air flow is established, the air pressure switch adjustment is made by 
turning the adjustment screw clockwise (See Figure 14) until the burner operation 
stops on the furnace. Slowly turn the adjustment screw counterclockwise until burner 
ignites. Make notice of the position of the adjustment screw, then turn the adjustment 
screw an additional 1/4 to 1/2 turn counterclockwise to ensure adequate switch 
adjustment. 

NOTE:

 

Under most circumstances, 1/4 turn is typical, however, 1/2 turn may be necessary to avoid short cycling due to 

extreme wind fluctuations.

 

WARNING: 

Failure to properly adjust the air pressure switch as specified in the proving switch section could lead to 

improper operation of the venting system which will result in product damage, personal injury, or death.

 

Figure 12

Figure 13

Figure 14

Summary of Contents for 46334800

Page 1: ...e burner and allows the burner to fire 2 After the heating requirement has been satisfied the thermostat circuit will open and de activate the burner 3 The power venter operates for a period of time a...

Page 2: ...ensure appliance efficiency This should be done at the appliance exhaust outlet with a velocity meter or draft gauge 7 On gas fired furnaces a barometric draft control must be installed to regulate p...

Page 3: ...n point shall not be installed closer than 3 from an inside corner of an L shaped structure f The vent termination should not be mounted directly above or within 3 horizontally from an oil tank vent o...

Page 4: ...pplicable local codes or appliance manufacturer s installation instructions Table 3 INSTALLATION CLEARANCE WITH SINGLE WALL VENT PIPE DOUBLE PIPE SYSTEM SINGLE PIPE VENTING SYSTEM Allowable Inlet Temp...

Page 5: ...and fasten using sheet metal screws See Figure 7 2 If using a Type B Vent Tee the opening of the Tee at the draft control mounting location should be sealed with a high temperature sealant or equivale...

Page 6: ...turned to their original position and properly fastened The wiring should be protected by an over current circuit device rated at 15 amperes CAUTION Power venter wiring must not come in contact with a...

Page 7: ...repeat steps 5 through 7 as necessary until proper draft is obtained and the draft control gate is in the proper position 9 Tighten the damper locking screw on the SWG to prevent it from moving durin...

Page 8: ...rs so they operate at maximum speed Do not operate a summer exhaust fan 3 Place in operation the appliance being inspected Follow the lighting instructions and adjust thermostat so appliance will oper...

Page 9: ...ctions if necessary Check the Power Venter choke plate to insure it is secured in place Check the barometric draft control to insure the gate swings freely 4 System Safety Devices With the heating sys...

Page 10: ...Page 10...

Page 11: ...LER S NAME _____________________________________________________ INSTALLER S COMPANY _________________________________________________ INSTALLER S PHONE NO ____________________________________________...

Page 12: ...Page 12 P N 46334800 Rev A 11 00...

Reviews: