SPECIAL VENTING APPLICATION 

INSTALLATION SHEET FOR

 

HEATERHUT WATER HEATER ENCLOSURES

 

 

This sheet covers the requirements for installing the Star-Kap™ on a 

HeaterHut

 gas water heater 

enclosure. The 

HeaterHut

 enclosure is designed for the purpose of housing a gas water heater 

outside of the living space of a structure. These requirements are based on the A.G.A. test reports 
FT-C-6-93 and FT-C-18-93. The 

HeaterHut

 water heater enclosure is not sold or manufactured by 

the Field Controls Co. These installation instructions only address the installation of the Star-Kap™, 
state the maximum capacity water heater allowed in an 

HeaterHut

 and the vent termination 

clearances from windows or openings into a building structure as tested in the A.G.A. field reports FT-
C-6-93 and FT-C-18-93. 
 

INSTALLATION GUIDE LINES 

1.  The maximum gas water heater appliance to be operated in a 

HeaterHut

 enclosure: up to 65,000 

BTU/HR input. 

2.  Two (2) make up/combustion air openings into the 

HeaterHut

 enclosure shall be installed. Each 

opening size shall be based on one (1) square inch per 4000 BTU/HR. The vent termination shall 
have the following clearance distances. 

a.  HH4034 Model 

HeaterHut

 

14” from combustible exterior wall to center of vent cap 

b.  HH5065 Model 

HeaterHut

 

16” from combustible exterior wall to center of vent cap 

c.  A minimum of 12” from any window or opening into the main building structure  
d.  A minimum of 18” below an eave or overhang 

 

STAR-KAP™ INSTALLATION 

Install one section of DOUBLE Wall vent pipe on top of water heater vent outlet and extend through 
roof of 

HeaterHut

 to a height as required by local codes. Then install a storm collar over vent pipe 

and push down until it rest of top of 

HeaterHut

 roof, caulk around storm collar if desired. Install Star-

Kap™ on top of vent pipe and secure with three self-tapping sheet metal screws. (See Figure 1) 

Figure 1

 

P/N 46357800 Rev A 11/00