Max. Equivalent Length of Pipe, Including StarKap

©

 

CAS-6 OIL 

(gph) 

CAS-6 GAS 

(BTU/hr) 

8” duct 

10” duct 

12” duct 

3 420,000  410 

1253  3119 

3.25 455,000 

344 

1051  2616 

3.5 490,000  291 

890  2217 

3.75 525,000 

249 

760 

1893 

4 560,000  214 

653  1627 

4.25 595,000 

185 

584 

1405 

4.5 630,000  160 

489  1217 

4.75 665,000 

139 

424 

1057 

5 700,000  121 

369  919 

5.25 735,000 

105 

321 

800 

5.75 805,000 

79 

241 

601 

6 840,000  58 

176  519 

6.5 910,000 

49 

151 

377 

CAS-7 OIL 

(gph) 

CAS-7 GAS 

(BTU/hr) 

10” duct 

12”duct 

14” duct 

6 840,000  469 

1167  2523 

6.5 910,000  381 

948  2050 

7 980,000  311 

776  1678 

7.5 1,050,000  256 

637 

1378 

8.25 1,155,000 

191 

476 

1029 

9 1,260,000  142 

354 

766 

9.75 1,365,000 

104 

260 

563 

10.5 1,470,000 

74 

186 

403 

11.25 1,575,000 

51 

127 

274 

12 1,680,000  31 

78 

207 

12.75 1,785,000 

15 

39 

114 

12.88 1,803,000 

13 

33 

72 

 
 

 

Page 4

Summary of Contents for 46371700

Page 1: ...gency in accordance with the manufacturers installation instructions The definition of a qualified agency is any individual firm corporation or company which either in person or through a representati...

Page 2: ...ng the horizontal axis and draw a vertical line through this point 5 The line should pass through at least one of the pipe size regions on the table The regions correspond to the maximum equivalent le...

Page 3: ...IPE 6 PIPE 8 PIPE 6 DUCT REGION 8 DUCT REGION 10 DUCT REGION 12 DUCT REGION Diagram A DIAGRAM B CAS 7 FAN STARKAP SK 12 SIZING CHART MAX EQUIVALENT FEET OF PIPE 0 0 25 0 50 0 75 0 100 0 125 0 150 0 17...

Page 4: ...9 424 1057 5 700 000 121 369 919 5 25 735 000 105 321 800 5 75 805 000 79 241 601 6 840 000 58 176 519 6 5 910 000 49 151 377 CAS 7 OIL gph CAS 7 GAS BTU hr 10 duct 12 duct 14 duct 6 840 000 469 1167...

Page 5: ...g pipe of different diameter than the CAS component connections attach increaser reducer fittings as close to the CAS unit and to the StarKap as possible The duct should be supported with appropriate...

Page 6: ...AS unit Refer to Figure 6 for connecting a single 120 VAC appliance to the CAS or Figure 7 for 24 VAC The three wires BURNER WHITE and ORANGE in Figure 4 correspond to the same wires shown in Figures...

Page 7: ...Figure 7 Figure 8 Page 7...

Page 8: ...Figure 9 Figure 10 Page 8...

Page 9: ...Figure 11 Figure 12 Page 9...

Page 10: ...ly CAUTION A minimum clearance of 1 must be maintained between the bottom of the fan blade and the top of the metal surface underneath FAILURE TO MAINTAIN THIS CLEARANCE MAY RESULT IN A FIRE HAZARD AN...

Page 11: ...Page 11...

Page 12: ...Page 12 P N 46371700 Rev B 06 06...

Reviews: