background image

 

Page 2

THE PURPOSE OF THE VACUUM 
RELIEF VALVE (VRV) 

The Vacuum Relief Valve is a safety 
device to guard against combustion 
problems associated with directly 
connecting oil burners to the outside.  
Typical problems can be caused by 
blockage of the intake termination, icing 
up of the ductwork and effects of leeward 
side wind effects on a building. 

VRV OPERATION 

The VRV gate operates on changes in the 
vacuum pressure generated by the inlet to 
the oil burner.  The VRV gate will remain 
closed during normal burner operation.  
During an abnormal operation (i.e., blockage of the intake or 
change in external building pressures) an increased negative 
pressure on the intake of the burner causes a reduction in 
burner airflow.  Under this condition, the VRV gate opens, 
stabilizing and maintaining proper airflow to the burner.  The 
VRV gate closes again once the abnormal condition is 
corrected. 

INSTALLATION

 

1.  Before the Furnace Boot™ can be mounted, a rectangular 

hole (2 ½” X 6”) must be located and cut into the side of the 
furnace cabinet.  The hole is located from the center of the 
burner intake. (See Figure 1) 

2.  Remove the oil pump and air bands from the burner 

housing!  Install the sealing gaskets onto the burner 
housing. (See Figure 2)  Replace existing pump coupling 
with the coupling supplied with the Furnace Boot™.  
Position the Furnace Boot™ over intake on the burner 
housing.  Align the holes in the Furnace Boot™ with the 
holes in the housing and re-attach the oil pump. (See 
Figure 3)  

Note: 

Replace pump coupling with the coupling 

supplied with kit.

 The Furnace Boot™ extension is mounted 

from the outside of the furnace cabinet and can be 
mounted to allow the routing of the duct pipe from the 
ceiling or from the floor. (See Figure 4) Assemble VRV 
balance weight onto the gate.  Screw the weight all the way 
in.  Then attach lock nut and knurl nut. (See Figure 4) 

Figure 1

 

Figure 2

 

 

Figure 3 

Figure 4

Summary of Contents for 46381400

Page 1: ...s for use only on the designated burner s as described in these instructions only when the specific burner includes this Furnace Boot when shipped from the burner manufacturer or where the burner instructions specifically reference the model CAS 2B 90E Furnace Boot as an optional air intake system ITEMS INCLUDED IN KIT 1 90E Furnace Boot 1 Set of Gaskets 1 4 VRV 1 4 IAH Hood 1 Burner Coupling Set ...

Page 2: ...ain once the abnormal condition is corrected INSTALLATION 1 Before the Furnace Boot can be mounted a rectangular hole 2 X 6 must be located and cut into the side of the furnace cabinet The hole is located from the center of the burner intake See Figure 1 2 Remove the oil pump and air bands from the burner housing Install the sealing gaskets onto the burner housing See Figure 2 Replace existing pum...

Page 3: ...y in Then attach lock nut and knurl nut See Figure 7 6 Mount the VRV assembly onto the tee and fasten with a screw and nut in collar tabs To ensure proper operation check the gate for being level across the pivot points and plumb See Figure 8 7 Refer to Figure 9 for general installation layout TERMINATION LOCATION GUIDELINES 1 Mount intake hood 12 inches above finished grade If mounting on the sid...

Page 4: ...ocal codes 4 To reduce uncontrolled air leakage into the duct tape all joints and seams using standard duct tape NOTE To prevent sweating on the outside of the duct when operating in areas that have 10 F or below design temperatures insulate the duct work at least 10 feet from the inlet vent termination OPERATION AIR ADJUSTMENT 1 Adjust the air adjustment knob on the side of the Furnace Boot See T...

Reviews: