24 VAC SYSTEM CONTROL KIT  

Model:

 CK-92FVP and CK-92FGP 

Designed for use with the SWG Series Power Venter for controlling 
Natural Gas or L.P. Gas appliances equipped with a 24 VAC 
automatic vent damper and a 30-millivolt controlled Natural or L.P. 
Gas Water Heater. 

 

I

TEMS INCLUDED IN KIT

:

 

1) Junction box with mounted pressure switch and post purge timer 
1) Fan control gas pressure switch with built in post purge option 
1) 2 ft. length of 1/4 inch aluminum tubing 
1) 1/8" NPT x 3 inch pipe nipple 
1) 1/8" NPT x 1/4 inch OD tubing elbow 
1) 1/8" NPT pipe tee 
1) TCA-1 Thermocouple Adaptor (CK-92FVP) 
1) TCA-2 Left Handed Thermocouple Adaptor (CK-92FGP) 
1) 6 ft. length of 12-2 wire 
1) 8 inch jumper wire 
2) Flexible conduit connector 
2) GSK-3 Spillage Switch 
1)  1/4 inch tubing connector 

WARNING:

  

Installer: if the 24V appliance does not have a blocked vent switch, an 

additional GSK-3P spillage switch kit, p/n 46458600, (not included) must be installed 
(See Diagram B).

 

DO NOT DESTROY 

THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT 

 

 

 

Summary of Contents for 46490500

Page 1: ...ost purge option 1 2 ft length of 1 4 inch aluminum tubing 1 1 8 NPT x 3 inch pipe nipple 1 1 8 NPT x 1 4 inch OD tubing elbow 1 1 8 NPT pipe tee 1 TCA 1 Thermocouple Adaptor CK 92FVP 1 TCA 2 Left Han...

Page 2: ...liance or nearby wall or floor joist through the four dimpled locations on the base of the box NOTE The mounted pressure switch diaphragm must be mounted with a vertical orientation see label on press...

Page 3: ...e 5 NOTE If installing on an existing appliance shut off gas supply to gas valve before plug removal 2 Replace the pressure tap plug with the 1 8 pipe nipple and pipe tee Install pressure tap plug at...

Page 4: ...power when wiring power venter Wire the venter motor and controls in accordance with the National Electrical Code manufacturer s recommendations and or applicable local codes UNITS MUST BE GROUNDED Ch...

Page 5: ...r conduit bracket If the damper has a round type motor assembly and does not have a conduit bracket See Diagram A install the supplied conduit bracket using the supplied 6 screws and nuts See Figure 1...

Page 6: ...nd burner 3 Wait 2 to 3 minutes Reset the spillage switches and light the pilot then perform a second safety spillage test Steps 1 and 2 CAUTION If for any reason the system has shut down during opera...

Page 7: ...ST MODEL PART NUMBER Gas Pressure Switch 46284200 GSK 3 Spillage Switch 46086400 Post Purge Timer 46282800 Pressure Switch 46273100 TCA 1 Thermocouple Adaptor 46082700 TCA 2 Left Handed Thermocouple A...

Page 8: ...R S NAME _____________________________________________________ INSTALLER S COMPANY _________________________________________________ INSTALLER S PHONE NO ______________________________________________...